Annexes to COM(2002)765 - Amendment of Directive 97/68/EC on the approximation of the laws of the Member States relating to measures against the emission of gaseous and particulate pollutants from internal combustion engines to be installed in non-road mobile machinery

Please note

This page contains a limited version of this dossier in the EU Monitor.

ANNEX I

1.ANNEX I SHALL BE AMENDED AS FOLLOWS:

1)SECTION 1 SHALL BE AMENDED AS FOLLOWS:

(a)Point A shall be replaced by the following:

"A.intended and suited, to move, or to be moved with or without road, and with

(i)a C.I. engine having a net power in accordance with section 2.4 that is higher than or equal to 19 kW but not more than 560 kW and that is operated under intermittent speed rather than a single constant speed;

or

(ii)a C.I. engine having a net power in accordance with section 2.4 that is higher than or equal to 19 kW but not more than 560 kW and that is operated under constant speed. Limits only apply from 31 December 2006;

or

(iii)a petrol fuelled S.I. engine having a net power in accordance with section 2.4 of not more than 19 kW;

or

(iv)engines designed for the propulsion of railcars, which are self propelled on-track vehicles specifically designed to carry goods and/or passengers;

or

(v)engines designed for the propulsion of locomotives which are self-propelled pieces of on-track equipment designed for moving or propelling cars that are designed to carry freight, passengers and other equipment, but which themselves are not designed or intended to carry freight, passengers (other than those operating the locomotive) or other equipment. Any auxiliary engine or engine intended to power equipment designed to perform maintenance or construction work on the tracks is not classified under this paragraph but under A(i).";

(b)Point B shall be replaced by the following:

""B.Ships, except vessels intended for use on inland waterways";

(c)Point C shall be deleted

2)Section 2 shall be amended as follows:

(a)The following shall be inserted:

"2.8a:volume of 100m3 or more with regard to a vessel intended for use on inland waterways means its volume calculated on the formula LxBxT, "L" being the maximum length of the hull, excluding rudder and bowsprit, "B" being the maximum breadth of the hull in metres, measured to the outer edge of the shell plating (excluding paddle wheels, rubbing strakes, etc.) and "T" being the vertical distance between the lowest moulded point of the hull or the keel and the maximum draught line.

2.8b:valid navigation or safety certificate shall mean:

(a)a certificate proving conformity with the 1974 International Convention for the Safety of Life at Sea (SOLAS), as amended, or equivalent, or

(b)a certificate proving conformity with the 1966 International Convention on Load Lines, as amended, or equivalent, and an IOPP certificate proving conformity with the 1973 International Convention for the Prevention of Pollution from Ships (MARPOL), as amended.

2.8c:Defeat device shall mean a device which measures, senses or responds to operating variables for the purpose of activating, modulating, delaying or deactivating the operation of any component or function of the emission control system such that the effectiveness of the control system is reduced under conditions encountered during the normal non-road mobile machinery use unless the use of such a device is substantially included in the applied emission test certification procedure.

2.8d:Irrational control strategy shall mean any strategy or measure that, when the non-road mobile machinery is operated under normal conditions of use, reduces the effectiveness of the emission control system to a level below that expected in the applicable emission test procedures."

(b)The following section shall be inserted:

"2.17test cycle shall mean a sequence of test points, each with a defined speed and torque, to be followed by the engine under steady state (NRSC test) or transient operating conditions (NRTC test);"

(c)Current Section 2.17 shall be renumbered 2.18 and be replaced by the following:

"2.18.   Symbols and abbreviations

2.18.1.   Symbols for test parameters

SymbolUnitTerm
A/Fst-Stoichiometric air/fuel ratio
APm2Cross sectional area of the isokinetic sampling probe
ATm2Cross sectional area of the exhaust pipe
AverWeighted average values for:
m3/h- volume flow
kg/h- mass flow
C1-Carbon 1 equivalent hydrocarbon
Cd-Discharge coefficient of the SSV
Concppm Vol%Concentration (with suffix of the component nominating)
Conccppm Vol%Background corrected concentration
Concdppm Vol%Concentration of the pollutant measured in the dilution air
Conceppm Vol%Concentration of the pollutant measured in the diluted exhaust gas
dmDiameter
DF-Dilution factor
fa-Laboratory atmospheric factor
GAIRDkg/hIntake air mass flow rate on dry basis
GAIRWkg/hIntake air mass flow rate on wet basis
GDILWkg/hDilution air mass flow rate on wet basis
GEDFWkg/hEquivalent diluted exhaust gas mass flow rate on wet basis
GEXHWkg/hExhaust gas mass flow rate on wet basis
GFUELkg/hFuel mass flow rate
GSEkg/hSampled exhaust mass flow rate
GTcm3/minTracer gas flow rate
GTOTWkg/hDiluted exhaust gas mass flow rate on wet basis
Hag/kgAbsolute humidity of the intake air
Hdg/kgAbsolute humidity of the dilution air
HREFg/kgReference value of absolute humidity (10,71 g/kg)
i-Subscript denoting an individual mode (for NRSC test)or an instananeous value (for NRTC test)
KH-Humidity correction factor for NOx
Kp-Humidity correction factor for particulate
KV-CFV calibration function
KW,a-Dry to wet correction factor for the intake air
KW,d-Dry to wet correction factor for the dilution air
KW,e-Dry to wet correction factor for the diluted exhaust gas
KW,r-Dry to wet correction factor for the raw exhaust gas
L%Percent torque related to the maximum torque for the test speed
MdmgParticulate sample mass of the dilution air collected
MDILkgMass of the dilution air sample passed through the particulate sampling filters
MEDFWkgMass of equivalent diluted exhaust gas over the cycle
MEXHWkgTotal exhaust mass flow over the cycle
MfmgParticulate sample mass collected
Mf,pmgParticulate sample mass collected on primary filter
Mf,bmgParticulate sample mass collected on back-up filter
MgasgTotal mass of gaseous pollutant over the cycle
MPTgTotal mass of particulate over the cycle
MSAMkgMass of the diluted exhaust sample passed through the particulate sampling filters
MSEkgSampled exhaust mass over the cycle
MSECkgMass of secondary dilution air
MTOTkgTotal mass of double diluted exhaust over the cycle
MTOTWkgTotal mass of diluted exhaust gas passing the dilution tunnel over the cycle on wet basis
MTOTW,IkgInstantaneous mass of diluted exhaust gas passing the dilution tunnel on wet basis
massg/hSubscript denoting emissions mass flow (rate)
NP-Total revolutions of PDP over the cycle
nrefmin-1Reference engine speed for NRTC test
s-2Derivative of the engine speed
PkWPower, brake uncorrected
p1kPaPressure drop below atmospheric at the pump inlet of PDP
PAkPaAbsolute pressure
PakPaSaturation vapour pressure of the engine intake air (ISO 3046: psy=PSY test ambient)
PAEkWDeclared total power absorbed by auxiliaries fitted for the test which are not required by paragraph 2.4 of this Annex
PBkPaTotal atmospheric pressure (ISO 3046:

Px=PX Site ambient total pressure

Py=PY Test ambient total pressure)
PdkPaSaturation vapour pressure of the dilution air
PMkWMaximum power at the test speed under test conditions (see Annex VII, Appendix 1)
PmkWPower measured on test bed
pskPaDry atmospheric pressure
q-Dilution ratio
Qsm3/sCVS volume flow rate
r-Ratio of the SSV throat to inlet absolute, static pressure
rRatio of cross sectional areas of isokinetic probe and exhaust pipe
Ra%Relative humidity of the intake air
Rd%Relative humidity of the dilution air
Re-Reynolds number
Rf-FID response factor
TKAbsolute temperature
tsMeasuring time
TaKAbsolute temperature of the intake air
TDKAbsolute dew point temperature
TrefKReference temperature of combustion air: (298 K)
TspN·mDemanded torque of the transient cycle
t10sTime between step input and 10% of final reading
t50sTime between step input and 50% of final reading
t90sTime between step input and 90% of final reading
ΔtisTime interval for instantaneous CFV flow
V0m3/revPDP volume flow rate at actual conditions
WactkWhActual cycle work of NRTC
WF-Weighting factor
WFE-Effective weighting factor
Xom3/revCalibration function of PDP volume flow rate
ΘDkg·m2Rotational inertia of the eddy-current dynamometer
ß-Ratio of the SSV throat diameter, d, to the inlet pipe inner diameter
λ-Relative air/fuel ratio, actual A/F divided by stoichiometric A/F
ρ EXHkg/m3Density of the exhaust gas

2.18.2.   Symbols for chemical components

CH4Methane
C3H8Propane
C2H6Ethane
COCarbon monoxide
CO2Carbon dioxide
DOPDi-octylphthalate
H2OWater
HCHydrocarbons
NOxOxides of nitrogen
NONitric oxide
NO2Nitrogen dioxide
O2Oxygen
PTParticulates
PTFEPolytetrafluoroethylene

2.18.3.   Abbreviations

CFVCritical Flow Venturi
CLDChemiluminescent detector
CICompression Ignition
FIDFlame Ionisation Detector
FSFull scale
HCLDHeated Chemiluminescent Detector
HFIDHeated Flame Ionisation Detector
NDIRNon-Dispersive Infrared Analyser
NGNatural Gas
NRSCNon-Road Steady Cycle
NRTCNon-Road Transient Cycle
PDPPositive Displacement Pump
SISpark Ignition
SSVSub-Sonic Venturi"

3)Section 3 shall be amended as follows:

(a)The following section shall be inserted:

"3.1.4.labels in accordance with Annex XIII, if the engine is placed on the market under flexible scheme provisions."

4)Section 4 is amended as follows:

(a)At the end of section 4.1.1. the following shall be added:

"All engines that expel exhaust gases mixed with water shall be equipped with a connection in the engine exhaust system that is located downstream of the engine and before any point at which the exhaust contacts water (or any other cooling/scrubbing medium) for the temporary attachment of gaseous or particulate emissions sampling equipment. It is important that the location of this connection allows a well mixed representative sample of the exhaust. This connection shall be internally threaded with standard pipe threads of a size not larger than one-half inch, and shall be closed by a plug when not in use (equivalent connections are allowed)."

(b)The following section shall be added:

"4.1.2.4.The emissions of carbon monoxide, the emissions of the sum of hydrocarbons and oxides of nitrogen and the emissions of particulates shall for stage III A not exceed the amounts shown in the table below:

Engines for use in other applications than propulsion of inland waterway vessels, locomotives and railcars:

Category: Net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Sum of hydrocarbons and oxides of nitrogen

(HC+NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
H: 130 kW ≤ P ≤ 560 kW3,54,00,2
I:75 kW ≤ P < 130 kW5,04,00,3
J: 37 kW ≤ P <75 kW5,04,70,4
K: 19 kW ≤ P < 37 kW5,57,50,6

Engines for propulsion of inland waterway vessels

Category: swept volume/net power

(SV/P)

(litres per cylinder/kW)
Carbon monoxide

(CO)

(g/kWh)
Sum of hydrocarbons and oxides of nitrogen

(HC+NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
V1:1 SV < 0,9 and P ≥ 37 kW5.07.50.40
V1:2 0,9≤SV< 1,25.07.20.30
V1:3 1,2≤SV< 2,55.07.20.20
V1:4 2,5≤SV< 55.07.20.20
V2:1 5≤SV<155.07.80.27
V2:2 15≤SV< 20 and P < 3300 kW5.08.70.50
V2:3 15≤SV< 20 and P ≥ 3300 kW5.09.80.50
V2:4 20≤SV< 255,09.80.50
V2:5 25≤SV< 305,011.00.50

Engines for propulsion of locomotives

Category: Net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Sum of hydrocarbons and oxides of nitrogen

(HC+NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
RL A: 130 kW ≤ P ≤ 560 kW3,54,00,2
Carbon monoxide

(CO)

(g/kWh)
Hydrocarbons

(HC)

(g/kWh)
Oxides of nitrogen

(NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
RH A: P > 560 kW3,50,56,00,2
RH A Engines with P > 2000 kW and SV> 5 l/cylinder3,50,47,40,2

Engines for propulsion of railcars

Category: net power (P) (kW)Carbon monoxide

(CO)

(g/kWh)
Sum of hydrocarbons and oxides of nitrogen

(HC+NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
RC A: 130 kW < P3,54,00,20

"

(c)The following section shall be inserted:

"4.1.2.5.The emissions of carbon monoxide, the emissions of hydrocarbons and oxides of nitrogen (or their sum where relevant) and the emissions of particulates shall, for stage III B, not exceed the amounts shown in the table below:

Engines for use in other applications than propulsion of locomotives, railcars and inland waterway vessels

Category: net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Hydrocarbons

(HC)

(g/kWh)
Oxides of nitrogen

(Nox)

(g/kWh)
Particulates

(PT)

(g/kWh)
L: 130 kW ≤ P ≤ 560 kW3,50,192,00,025
M: 75 kW ≤ P < 130 kW5,00,193,30,025
N: 56 kW ≤ P < 75 kW5,00,193,30,025
Sum of hydrocarbons and oxides ofnitrogen

(HC+NOx)

(g/kWh)
P: 37 kW ≤ P < 56 kW5,04,70,025

Engines for propulsion of railcars

Category: net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Hydrocarbons

(HC)

(g/kWh)
Oxides of nitrogen

(NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
RC B: 130 kW < P3,50.192,00,025

Engines for propulsion of locomotives:

Category: Net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Sum of hydrocarbons and oxides of nitrogen

(HC+NOx)

(g/kWh)
Particulates

(PT)

(g/kWh)
R B: 130 kW < P3,54,00,025

(d)The following section shall be inserted after the new section 4.1.2.5:

"4.1.2.6.The emissions of carbon monoxide, the emissions of hydrocarbons and oxides of nitrogen (or their sum where relevant) and the emissions of particulates shall for stage IV not exceed the amounts shown in the table below:

Engines for use in other applications than propulsion of locomotives, railcars and inland waterway vessels

Category: Net power

(P)

(kW)
Carbon monoxide

(CO)

(g/kWh)
Hydrocarbons

(HC)

(g/kWh)
Oxides of nitrogen

(NOx)(g/kWh)
Particulates

(PT)

(g/kWh)
Q: 130 kW ≤ P ≤ 560 kW3,50,190,40,025
R: 56 kW ≤ P < 130 kW5,00,190,40,025

"

(e)The following section shall be inserted:

"4.1.2.7.The limit values in sections 4.1.2.4, 4.1.2.5 and 4.1.2.6 shall include deterioration calculated in accordance with Annex III, appendix 5.

In the case of limit values standards contained in sections 4.1.2.5 and 4.1.2.6, under all randomly selected load conditions, belonging to a definite control area and with the exception of specified engine operating conditions which are not subject to such a provision, the emissions sampled during a time duration as small as 30 s shall not exceed by more than 100% the limit values of the above tables. The control area to which the percentage not to be exceeded shall apply and the excluded engine operating conditions shall be defined in accordance with the procedure referred to in Article 15."

(f)Section 4.1.2.4 shall be renumbered to 4.1.2.8

2.ANNEX III SHALL BE AMENDED AS FOLLOWS:

1)Section 1 shall be amended as follows:

(a)The following shall be added to section 1.1.:

"Two test cycles are described that shall be applied according to the provisions of Annex I, Section 1:

the NRSC (Non-Road Steady Cycle) which shall be used for stages I, II and IIIA and for constant speed engines as well as for stages IIIB and IV in the case of gaseous pollutants,

the NRTC (Non-Road Transient Cycle) which shall be used for the measurement of particulate emissions for stages IIIB and IV and for all engines but constant speed engines. By the choice of the manufacturer this test can be used also for stage IIIA and for the gaseous pollutants in stages IIIB and IV.

For engines intended to be used in inland waterway vessels the ISO test procedure as specified by ISO 8178-4:2002 [E] and IMO MARPOL 73/78, Annex VI (NOx Code) shall be used.

For engines intended for propulsion of railcars an NRSC shall be used for the measurement of gaseous and particulate pollutants for stage III A and for stage III B.

For engines intended for propulsion of locomotives an NRSC shall be used for the measurement of gaseous and particulate pollutants for stage III A and for stage III B."

(b)The following section shall be added:

"1.3.Measurement principle:

The engine exhaust emissions to be measured include the gaseous components (carbon monoxide, total hydrocarbons and oxides of nitrogen), and the particulates. Additionally, carbon dioxide is often used as a tracer gas for determining the dilution ratio of partial and full flow dilution systems. Good engineering practice recommends the general measurement of carbon dioxide as an excellent tool for the detection of measurement problems during the test run.

1.3.1.NRSC Test:

During a prescribed sequence of operating conditions, with the engines warmed up, the amounts of the above exhaust emissions shall be examined continuously by taking a sample from the raw exhaust gas. The test cycle consists of a number of speed and torque (load) modes, which cover the typical operating range of diesel engines. During each mode, the concentration of each gaseous pollutant, exhaust flow and power output shall be determined, and the measured values weighted. The particulate sample shall be diluted with conditioned ambient air. One sample over the complete test procedure shall be taken and collected on suitable filters.

Alternatively, a sample shall be taken on separate filters, one for each mode, and cycle-weighted results computed.

The grams of each pollutant emitted per kilowatt -hour shall be calculated as described in Appendix 3 to this Annex.

1.3.2.NRTC Test:

The prescribed transient test cycle, based closely on the operating conditions of diesel engines installed in non-road machinery, is run twice:

The first time (cold start) after the engine has soaked to room temperature and the engine coolant and oil temperatures, after treatment systems and all auxiliary engine control devices are stabilised between 20 and 30oC.

The second time (hot start) after a twenty-minute hot soak that commences immediately after the completion of the cold start cycle.

During this test sequence the above pollutants shall be examined. Using the engine torque and speed feedback signals of the engine dynamometer, the power shall be integrated with respect to the time of the cycle, resulting in the work produced by the engine over the cycle. The concentrations of the gaseous components shall be determined over the cycle, either in the raw exhaust gas by integration of the analyzer signal in accordance with Appendix 3 to this Annex, or in the diluted exhaust gas of a CVS full-flow dilution system by integration or by bag sampling in accordance with Appendix 3 to this Annex. For particulates, a proportional sample shall be collected from the diluted exhaust gas on a specified filter by either partial flow dilution or full-flow dilution. Depending on the method used, the diluted or undiluted exhaust gas flow rate shall be determined over the cycle to calculate the mass emission values of the pollutants. The mass emission values shall be related to the engine work to give the grams of each pollutant emitted per kilowatt-hour.

Emissions (g/kWh) shall be measured during both the cold and hot start cycles. Composite weighted emissions shall be computed by weighting the cold start results 10% and the hot start results 90%. Weighted composite results shall meet the standards.

Prior to the introduction of the cold/hot composite test sequence, the symbols (Annex I, section 2.18) the test sequence (Annex III) and calculation equations (Annex III, Appendix III) shall be modified in accordance with the procedure referred to in Article 15."

2)Section 2 shall be amended as follows:

(a)Section 2.2.3 shall be replaced by the following:

"2.2.3.Engines with charge air cooling

The charge air temperature shall be recorded and, at the declared rated speed and full load, shall be within ± 5 K of the maximum charge air temperature specified by the manufacturer. The temperature of the cooling medium shall be at least 293 K (20oC).

If a test shop system or external blower is used, the charge air temperature shall be set to within ± 5 K of the maximum charge air temperature specified by the manufacturer at the speed of the declared maximum power and full load. Coolant temperature and coolant flow rate of the charge air cooler at the above set point shall not be changed for the whole test cycle. The charge air cooler volume shall be based upon good engineering practice and typical vehicle/machinery applications.

Optionally, the setting of the charge air cooler may be done in accordance with SAE J 1937 as published in January 1995."

(b)The text under section 2.3 shall be replaced by the following:

"The test engine shall be equipped with an air inlet system presenting an air inlet restriction within ± 300 Pa of the value specified by the manufacturer for a clean air cleaner at the engine operating conditions as specified by the manufacturer, which result in maximum air flow. The restrictions are to be set at rated speed and full load. A test shop system may be used, provided it duplicates actual engine operating conditions."

(c)The text under section 2.4 Engine exhaust system shall be replaced by the following:

"The test engine shall be equipped with an exhaust system with exhaust back pressure within ± 650 Pa of the value specified by the manufacturer at the engine operating conditions resulting in maximum declared power.

If the engine is equipped with an exhaust after-treatment device, the exhaust pipe shall have the same diameter as found in-use for at least 4 pipe diameters upstream to the inlet of the beginning of the expansion section containing the after-treatment device. The distance from the exhaust manifold flange or turbocharger outlet to the exhaust after-treatment device shall be the same as in the machine configuration or within the distance specifications of the manufacturer. The exhaust backpressure or restriction shall follow the same criteria as above, and may be set with a valve. The aftertreatment container may be removed during dummy tests and during engine mapping, and replaced with an equivalent container having an inactive catalyst support."

(d)Section 2.8 shall be deleted.

3)Section 3 shall be amended as follows:

(a)The title of section 3 shall be replaced by:

"3.   

TEST RUN (NRSC TEST)"

(b)The following section shall be inserted:

"3.1.Determination of dynamometer settings

The basis of specific emissions measurement is uncorrected brake power according to ISO 14396: 2002.

Certain auxiliaries, which are necessary only for the operation of the machine and may be mounted on the engine, should be removed for the test. The following incomplete list is given as an example:

air compressor for brakes

power steering compressor

air conditioning compressor

pumps for hydraulic actuators.

Where auxiliaries have not been removed, the power absorbed by them at the test speeds shall be determined in order to calculate the dynamometer settings, except for engines where such auxiliaries form an integral part of the engine (e.g. cooling fans for air cool engines).

The settings of inlet restriction and exhaust pipe backpressure shall be adjusted to the manufacturer's upper limits, in accordance with sections 2.3 and 2.4.

The maximum torque values at the specified test speeds shall be determined by experimentation in order to calculate the torque values for the specified test modes. For engines which are not designed to operate over a range on a full load torque curve, the maximum torque at the test speeds shall be declared by the manufacturer.

The engine setting for each test mode shall be calculated using the formula:



If the ratio,



the value of PAE may be verified by the technical authority granting type approval."

(c)Current sections 3.1 - 3.3 shall be renumbered 3.2 - 3.4

(d)Current section 3.4 shall be renumbered 3.5 and replaced by the following:

"3.5.Adjustment of the dilution ratio

The particulate sampling system shall be started and running on bypass for the single filter method (optional for the multiple filter method). The particulate background level of the dilution air may be determined by passing dilution air through the particulate filters. If filtered dilution air is used, one measurement may be done at any time prior to, during, or after the test. If the dilution air is not filtered, the measurement must be done on one sample taken for the duration of the test.

The dilution air shall be set to obtain a filter face temperature between 315 K (42oC) and 325 K (52oC) at each mode. The total dilution ratio shall not be less than four.

NOTE: For steady-state procedure, the filter temperature may be kept at or below the maximum temperature of 325 K (52oC) instead of respecting the temperature range of 42oC - 52oC.

For the single and multiple filter methods, the sample mass flow rate through the filter shall be maintained at a constant proportion of the dilute exhaust mass flow rate for full flow systems for all modes. This mass ratio shall be within ± 5% with respect to the averaged value of the mode, except for the first 10 seconds of each mode for systems without bypass capability. For partial flow dilution systems with single filter method, the mass flow rate through the filter shall be constant within ± 5% with respect to the averaged value of the mode, except for the first 10 seconds of each mode for systems without bypass capability.

For CO2 or NOx concentration controlled systems, the CO2 or NOx content of the dilution air must be measured at the beginning and at the end of each test. The pre and post test background CO2 or NOx concentration measurements of the dilution air must be within 100 ppm or 5 ppm of each other, respectively.

When using a dilute exhaust gas analysis system, the relevant background concentrations shall be determined by sampling dilution air into a sampling bag over the complete test sequence.

Continuous (non-bag) background concentration may be taken at the minimum of three points, at the beginning, at the end, and a point near the middle of the cycle and averaged. At the manufacturer's request background measurements may be omitted."

(e)Current sections 3.5-3.6 shall be renumbered 3.6-3.7.

(f)Current sections 3.6.1 shall be replaced by the following:

"3.7.1.Equipment specification according to Section 1A of Annex I:

3.7.1.1.Specification A.

For engines covered by Section 1A(i) and A(iv) of Annex I, the following 8-mode cycle (1) shall be followed in dynamometer operation on the test engine:

Mode NumberEngine SpeedLoadWeighting Factor
1Rated1000,15
2Rated750,15
3Rated500,15
4Rated100,10
5Intermediate1000,10
6Intermediate750,10
7Intermediate500,10
8Idle---0,15

3.7.1.2.Specification B.

For engines covered by Section lA(ii) of Annex I, the following 5-mode cycle (2) shall be followed in dynamometer operation on the test engine:

Mode NumberEngine SpeedLoadWeighting Factor
1Rated1000,05
2Rated750,25
3Rated500,30
4Rated250,30
5Rated100,10

The load figures are percentage values of the torque corresponding to the prime power rating defined as the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year, between stated maintenance intervals and under the stated ambient conditions, the maintenance being carried out as prescribed by the manufacturer.

3.7.1.3Specification C.

For propulsion engines (3) intended to be used in inland waterway vessels the ISO test procedure as specified by ISO 81784:2002(E) and IMO MARPOL 73/78, Annex VI (NOx Code) shall be used.

Propulsion engines that operate on a fixed-pitch propeller curve shall be tested on a dynamometer using the following 4-mode steady-state cycle (4) developed to represent in-use operation of commercial marine diesel engines:

Mode NumberEngine SpeedLoadWeighting Factor
1100%

(Rated)
1000,20
291%750,50
380%500,15
463%250,15

Fixed speed inland waterway propulsion engines with variable pitch or electrically coupled propellers shall be tested on a dynamometer using the following 4-mode steady-state cycle (5) characterised by the same load and weighting factors as the above cycle, but with engine operated in each mode at rated speed:

Mode NumberEngine SpeedLoadWeighting Factor
1Rated1000,20
2Rated750,50
3Rated500,15
4Rated250,15

3.7.1.4.Specification D

For engines covered by Section 1A(v) of Annex I, the following 3-mode cycle (6) shall be followed in dynamometer operation on the test engine:

Mode NumberEngine SpeedLoadWeighting Factor
1Rated1000,25
2Intermediate500,15
3Idle-0,60

(g)Current section 3.7.3. shall be replaced by the following:

"The test sequence shall be started. The test shall be performed in the order of the mode numbers as set out above for the test cycles.

During each mode of the given test cycle after the initial transition period, the specified speed shall be held to within ±1% of rated speed or ± 3 min-1, whichever is greater, except for low idle which shall be within the tolerances declared by the manufacturer. The specified torque shall be held so that the average over the period during which the measurements are being taken is within ± 2% of the maximum torque at the test speed.

For each measuring point a minimum time of 10 minutes is necessary. If for the testing of an engine, longer sampling times are required for reasons of obtaining sufficient particulate mass on the measuring filter the test mode period can be extended as necessary.

The mode length shall be recorded and reported.

The gaseous exhaust emission concentration values shall be measured and recorded during the last three minutes of the mode.

The particulate sampling and the gaseous emission measurement should not commence before engine stabilisation, as defined by the manufacturer, has been achieved and their completion must be coincident.

The fuel temperature shall be measured at the inlet to the fuel injection pump or as specified by the manufacturer, and the location of measurement recorded."

(h)The current section 3.7 shall be renumbered 3.8.

4)The following section shall be inserted:

"4.   TEST RUN (NRTC TEST)

4.1.   Introduction

The non-road transient cycle (NRTC) is listed in Annex III, Appendix 4 as a second-by-second sequence of normalized speed and torque values applicable to all diesel engines covered by this Directive. In order to perform the test on an engine test cell, the normalised values shall be converted to the actual values for the individual engine under test, based on the engine mapping curve. This conversion is referred to as denormalisation, and the test cycle developed is referred to as the reference cycle of the engine to be tested. With these reference speed and torque values, the cycle shall be run on the test cell, and the feedback speed and torque values recorded. In order to validate the test run, a regression analysis between reference and feedback speed and torque values shall be conducted upon completion of the test.

4.1.1.The use of defeat devices or irrational control or irrational emission control strategies shall be prohibited

4.2.   Engine mapping procedure

When generating the NRTC on the test cell, the engine shall be mapped before running the test cycle to determine the speed vs torque curve.

4.2.1.   Determination of the mapping speed range

The minimum and maximum mapping speeds are defined as follows:

Minimum mapping speed=idle speed
Maximum mapping speed=nhi x 1,02 or speed where full load torque drops off to zero, whichever is lower

(where nhi is the high speed, defined as the highest engine speed where 70% of the rated power is delivered).

4.2.2.   Engine mapping curve

The engine shall be warmed up at maximum power in order to stabilise the engine parameters according to the recommendation of the manufacturer and good engineering practice. When the engine is stabilised, the engine mapping shall be performed according to the following procedures.

4.2.2.1.   Transient map

(a)The engine shall be unloaded and operated at idle speed.

(b)The engine shall be operated at full load setting of the injection pump at minimum mapping speed.

(c)The engine speed shall be increased at an average rate of 8 ± 1 min-1 /s from minimum to maximum mapping speed. Engine speed and torque points shall be recorded at a sample rate of at least one point per second.

4.2.2.2.   Step map

(a)The engine shall be unloaded and operated at idle speed.

(b)The engine shall be operated at full load setting of the injection pump at minimum mapping speed.

(c)While maintaining full load, the minimum mapping speed shall be maintained for at least 15 s, and the average torque during the last 5 s shall be recorded. The maximum torque curve from minimum to maximum mapping speed shall be determined in no greater than 100 ± 20 /min speed increments. Each test point shall be held for at least 15 s, and the average torque during the last 5 s shall be recorded.

4.2.3.   Mapping curve generation

All data points recorded under section 4.2.2 shall be connected using linear interpolation between points. The resulting torque curve is the mapping curve and shall be used to convert the normalized torque values of the engine dynamometer schedule of Annex IV into actual torque values for the test cycle, as described in section 4.3.3.

4.2.4.   Alternate mapping

If a manufacturer believes that the above mapping techniques are unsafe or unrepresentative for any given engine, alternate mapping techniques may be used. These alternate techniques must satisfy the intent of the specified mapping procedures to determine the maximum available torque at all engine speeds achieved during the test cycles. Deviations from the mapping techniques specified in this section for reasons of safety or representativeness shall be approved by the parties involved along with the justification for their use. In no case, however, shall the torque curve be run by descending engine speeds for governed or turbocharged engines.

4.2.5.   Replicate tests

An engine need not be mapped before each and every test cycle. An engine must be remapped prior to a test cycle if:

an unreasonable amount of time has transpired since the last map, as determined by engineering judgement,

or,

physical changes or recalibrations have been made to the engine, which may potentially affect engine performance.

4.3.   Generation of the reference test cycle

4.3.1.   Reference speed

The reference speed (nref) corresponds to the 100% normalized speed values specified in the engine dynamometer schedule of Annex III, Appendix 4. It is obvious that the actual engine cycle resulting from denormalization to the reference speed largely depends on selection of the proper reference speed. The reference speed shall be determined by the following definition:

nref = low speed + 0,95 x (high speed - low speed)

(the high speed is the highest engine speed where 70% of the rated power is delivered, while the low speed is the lowest engine speed where 50% of the rated power is delivered).

4.3.2.   Denormalization of engine speed

The speed shall be denormalized using the following equation:



4.3.3.   Denormalization of engine torque

The torque values in the engine dynamometer schedule of Annex III, Appendix 4 are normalized to the maximum torque at the respective speed. The torque values of the reference cycle shall be denormalized, using the mapping curve determined according to Section 4.2.2, as follows:



for the respective actual speed as determined in Section 4.3.2.

4.3.4.   Example of denormalization procedure

As an example, the following test point shall be denormalized:

% speed = 43%

% torque = 82%

Given the following values:

reference speed = 2200 /min

idle speed = 600 /min

results in



With the maximum torque of 700 Nm observed from the mapping curve at 1288 /min



4.4.   Dynamometer

4.4.1.When using a load cell, the torque signal shall be transferred to the engine axis and the inertia of the dyno shall be considered. The actual engine torque is the torque read on the load cell plus the moment of inertia of the brake multiplied by the angular acceleration. The control system has to perform this calculation in real time.

4.4.2.If the engine is tested with an eddy-current dynamometer, it is recommended that the number of points, where the difference



is smaller than - 5% of the peak torque, does not exceed 30 (where Tsp is the demanded torque,



is the derivative of the engine speed and· ΘD is the rotational inertia of the eddy-current dynamometer).

4.5.   Emissions test run

The following flow chart outlines the test sequence.



One or more Practice Cycles may be run as necessary to check engine, test cell and emissions systems before the measurement cycle.

4.5.1.   Preparation of the sampling filters

At least one hour before the test, each filter shall be placed in a petri dish, which is protected against dust contamination and allows air exchange, and placed in a weighing chamber for stabilization. At the end of the stabilization period, each filter shall be weighed and the weight shall be recorded. The filter shall then be stored in a closed petri dish or sealed filter holder until needed for testing. The filter shall be used within eight hours of its removal from the weighing chamber. The tare weight shall be recorded.

4.5.2.   Installation of the measuring equipment

The instrumentation and sample probes shall be installed as required. The tailpipe shall be connected to the full flow dilution system, if used.

4.5.3.   Starting and preconditioning the dilution system and the engine

The dilution system and the engine shall be started and warmed up. The sampling system preconditioning shall be conducted by operating the engine at a condition of rated-speed, 100 percent torque for a minimum of 20 minutes while simultaneously operating either the Partial flow Sampling System or the Full flow CVS with secondary dilution system. Dummy particulate matter emissions samples are then collected. Particulate sample filters need not be stabilized or weighed, and may be discarded. Filter media may be changed during conditioning as long as the total sampled time through the filters and sampling system exceeds 20 minutes. Flow rates shall be set at the approximate flow rates selected for transient testing. Torque shall be reduced from 100 percent torque while maintaining the rated speed condition as necessary so as not to exceed the 191 o C maximum sample zone temperature specifications.

4.5.4.   Starting the particulate sampling system

The particulate sampling system shall be started and run on by-pass. The particulate background level of the dilution air may be determined by sampling the dilution air prior to entrance of the exhaust into the dilution tunnel. It is preferred that background particulate sample be collected during the transient cycle if another PM sampling system is available. Otherwise, the PM sampling system used to collect transient cycle PM can be used. If filtered dilution air is used, one measurement may be done prior to or after the test. If the dilution air is not filtered, measurements should be carried out prior to the beginning and after the end of the cycle and the values averaged.

4.5.5.   Adjustment of the dilution system

The total diluted exhaust gas flow of a full flow dilution system or the diluted exhaust gas flow through a partial flow dilution system shall be set to eliminate water condensation in the system, and to obtain a filter face temperature between 315 K (42oC) and 325 K (52oC).

4.5.6.   Checking the analyzers

The emission analyzers shall be set at zero and spanned. If sample bags are used, they shall be evacuated.

4.5.7.   Engine starting procedure

The stabilized engine shall be started within 5 min after completion of warm-up according to the starting procedure recommended by the manufacturer in the owner's manual, using either a production starter motor or the dynamometer. Optionally, the test may start within 5 min of the engine preconditioning phase without shutting the engine off, when the engine has been brought to an idle condition.

4.5.8.   Cycle run

4.5.8.1.   Test sequence

The test sequence shall commence when the engine is started from shut down after the preconditioning phase or from idle conditions when starting directly from the preconditioning phase with the engine running. The test shall be performed according to the reference cycle as set out in Annex III, Appendix 4. Engine speed and torque command set points shall be issued at 5 Hz (10 Hz recommended) or greater. The set points shall be calculated by linear interpolation between the 1 Hz set points of the reference cycle. Feedback engine speed and torque shall be recorded at least once every second during the test cycle, and the signals may be electronically filtered.

4.5.8.2.   Analyzer response

At the start of the engine or test sequence, if the cycle is started directly from preconditioning, the measuring equipment shall be started, simultaneously:

start collecting or analyzing dilution air, if a full flow dilution system is used;

start collecting or analyzing raw or diluted exhaust gas, depending on the method used;

start measuring the amount of diluted exhaust gas and the required temperatures and pressures;

start recording the exhaust gas mass flow rate, if raw exhaust gas analysis is used;

recording the feedback data of speed and torque of the dynamometer.

If raw exhaust measurement is used, the emission concentrations (HC, CO and NOx) and the exhaust gas mass flow rate shall be measured continuously and stored with at least 2 Hz on a computer system. All other data may be recorded with a sample rate of at least 1 Hz. For analogue analyzers the response shall be recorded, and the calibration data may be applied online or offline during the data evaluation.

If a full flow dilution system is used, HC and NOx shall be measured continuously in the dilution tunnel with a frequency of at least 2 Hz. The average concentrations shall be determined by integrating the analyzer signals over the test cycle. The system response time shall be no greater than 20 s, and shall be coordinated with CVS flow fluctuations and sampling time/test cycle offsets, if necessary. CO and CO2 shall be determined by integration or by analyzing the concentrations in the sample bag collected over the cycle. The concentrations of the gaseous pollutants in the dilution air shall be determined by integration or by collection in the background bag. All other parameters that need to be measured shall be recorded with a minimum of one measurement per second (1 Hz).

4.5.8.3.   Particulate sampling

At the start of the engine or test sequence, if the cycle is started directly from preconditioning, the particulate sampling system shall be switched from by-pass to collecting particulates.

If a partial flow dilution system is used, the sample pump(s) shall be adjusted so that the flow rate through the particulate sample probe or transfer tube is maintained proportional to the exhaust mass flow rate.

If a full flow dilution system is used, the sample pump(s) shall be adjusted so that the flow rate through the particulate sample probe or transfer tube is maintained at a value within ± 5% of the set flow rate. If flow compensation (i.e., proportional control of sample flow) is used, it must be demonstrated that the ratio of main tunnel flow to particulate sample flow does not change by more than ± 5% of its set value (except for the first 10 seconds of sampling).

NOTE: For double dilution operation, sample flow is the net difference between the flow rate through the sample filters and the secondary dilution airflow rate.

The average temperature and pressure at the gas meter(s) or flow instrumentation inlet shall be recorded. If the set flow rate cannot be maintained over the complete cycle (within ± 5%) because of high particulate loading on the filter, the test shall be voided. The test shall be rerun using a lower flow rate and/or a larger diameter filter.

4.5.8.4.   Engine stalling

If the engine stalls anywhere during the test cycle, the engine shall be preconditioned and restarted, and the test repeated. If a malfunction occurs in any of the required test equipment during the test cycle, the test shall be voided.

4.5.8.5.   Operations after test

At the completion of the test, the measurement of the exhaust gas mass flow rate, the diluted exhaust gas volume, the gas flow into the collecting bags and the particulate sample pump shall be stopped. For an integrating analyzer system, sampling shall continue until system response times have elapsed.

The concentrations of the collecting bags, if used, shall be analyzed as soon as possible and in any case not later than 20 minutes after the end of the test cycle.

After the emission test, a zero gas and the same span gas shall be used for re-checking the analyzers. The test will be considered acceptable if the difference between the pre-test and post-test results is less than 2% of the span gas value.

The particulate filters shall be returned to the weighing chamber no later than one hour after completion of the test. They shall be conditioned in a petri dish, which is protected against dust contamination and allows air exchange, for at least one hour, and then weighed. The gross weight of the filters shall be recorded.

4.6.   Verification of the test run

4.6.1.   Data Shift

To minimise the biasing effect of the time lag between the feedback and reference cycle values, the entire engine speed and torque feedback signal sequence may be advanced or delayed in time with respect to the reference speed and torque sequence. If the feedback signals are shifted, both speed and torque must be shifted by the same amount in the same direction.

4.6.2.   Calculation of the Cycle Work

The actual cycle work Wact (kWh) shall be calculated using each pair of engine feedback speed and torque values recorded. The actual cycle work Wact is used for comparison to the reference cycle work Wref and for calculating the brake specific emissions. The same methodology shall be used for integrating both reference and actual engine power. If values are to be determined between adjacent reference or adjacent measured values, linear interpolation shall be used.

In integrating the reference and actual cycle work, all negative torque values shall be set equal to zero and included. If integration is performed at a frequency of less than 5 Hertz, and if, during a given time segment, the torque value changes from positive to negative or negative to positive, the negative portion shall be computed and set equal to zero. The positive portion shall be included in the integrated value.

Wact shall be between -15% and + 5% of Wref.

4.6.3.   Validation Statistics of the Test Cycle

Linear regressions of the feedback values on the reference values shall be performed for speed, torque and power. This shall be done after any feedback data shift has occurred, if this option is selected. The method of least squares shall be used, with the best fit equation having the form:

y = mx + b

where:

y=feedback (actual) value of speed (min-1), torque (N·m), or

power (kW)
m=slope of the regression line
x=reference value of speed (min-1), torque (N·m), or power (kW)
b=y intercept of the regression line

The standard error of estimate (SE) of y on x and the coefficient of determination (r2) shall be calculated for each regression line.

It is recommended that this analysis be performed at 1 Hertz. For a test to be considered valid, the criteria of Table 1 must be met.

Table 1: Regression Line Tolerances

SpeedTorquePower
Standard error of estimate (SE) of Y on Xmax 100 min-1max 13 % of power map

maximum engine torque
max 8% of power map

maximum engine power
Slope of the regression line, m0,95 to 1,030,83 - 1,030,89 - 1,03
Coefficient of determination, r2min 0,9700min 0,8800min 0,9100
Y intercept of the regression line, b± 50 min-1± 20 N·m or ± 2% of max torque, whichever is greater± 4 kW or ± 2% of max power, whichever is greater

For regression purposes only, point deletions are permitted where noted in Table 2 before doing the regression calculation. However, those points must not be deleted for the calculation of cycle work and emissions. An idle point is defined as a point having a normalized reference torque of 0% and a normalized reference speed of 0%. Point deletion may be applied to the whole or to any part of the cycle.

Table 2. Permitted Point Deletions From Regression Analysis

(points to which the point deletion is applied have to be specified)

CONDITIONSPEED AND/OR TORQUE AND/OR POWER POINTS WHICH MAY BE DELETED WITH REFERENCE TO THE CONDITIONS LISTED IN THE LEFT COLUMN
First 24 (±1) sand last 25 sSpeed, torque and power
Wide open throttle, and torque feedback < 95% torque referenceTorque and/or power
Wide open throttle, and speed feedback < 95% speed referenceSpeed and/or power
Closed throttle, speed feedback > idle speed + 50 min-1, and torque feedback > 105% torque referenceTorque and/or power
Closed throttle, speed feedback = idle speed + 50 min-1, and torque feedback = Manufacturer defined/measured idle torque ± 2% of max torqueSpeed and/or power
Closed throttle and speed feedback > 105% speed referenceSpeed and/or power"

5)Appendix 1 shall be replaced by the following:

"APPENDIX 1

MEASUREMENT AND SAMPLING PROCEDURES

1. MEASUREMENT AND SAMPLING PROCEDURES (NRSC TEST)

Gaseous and particulate components emitted by the engine submitted for testing shall be measured by the methods described in Annex VI. The methods of Annex VI describe the recommended analytical systems for the gaseous emissions (Section 1.1) and the recommended particulate dilution and sampling systems (Section 1.2).

1.1.   Dynamometer specification

An engine dynamometer with adequate characteristics to perform the test cycle described in Annex III, Section 3.7.1 shall be used. The instrumentation for torque and speed measurement shall allow the measurement of the power within the given limits. Additional calculations may be necessary. The accuracy of the measuring equipment must be such that the maximum tolerances of the figures given in point 1.3 are not exceeded.

1.2.   Exhaust gas flow

The exhaust gas flow shall be determined by one of the methods mentioned in sections 1.2.1 to 1.2.4.

1.2.1.   Direct measurement method

Direct measurement of the exhaust flow by flow nozzle or equivalent metering system (for detail see ISO 5167:2000).

NOTE: Direct gaseous flow measurement is a difficult task. Precautions must be taken to avoid measurement errors that will impact emission value errors.

1.2.2.   Air and fuel measurement method

Measurement of the airflow and the fuel flow.

Air flow-meters and fuel flow-meters with the accuracy defined in Section 1.3 shall be used.

The calculation of the exhaust gas flow is as follows:

GEXHW = GAIRW + GFUEL (for wet exhaust mass)

1.2.3.   Carbon balance method

Exhaust mass calculation from fuel consumption and exhaust gas concentrations using the carbon balance method (Annex III, Appendix 3).

1.2.4.   Tracer measurement method

This method involves measurement of the concentration of a tracer gas in the exhaust.

A known amount of an inert gas (e.g. pure helium) shall be injected into the exhaust gas flow as a tracer. The gas is mixed and diluted by the exhaust gas, but must not react in the exhaust pipe. The concentration of the gas shall then be measured in the exhaust gas sample.

In order to ensure complete mixing of the tracer gas, the exhaust gas sampling probe shall be located at least 1 m or 30 times the diameter of the exhaust pipe, whichever is larger, downstream of the tracer gas injection point. The sampling probe may be located closer to the injection point if complete mixing is verified by comparing the tracer gas concentration with the reference concentration when the tracer gas is injected upstream of the engine.

The tracer gas flow rate shall be set so that the tracer gas concentration at engine idle speed after mixing becomes lower than the full scale of the trace gas analyzer.

The calculation of the exhaust gas flow is as follows:



where

GEXHW=instantaneous exhaust mass flow (kg/s)
GT=tracer gas flow (cm3/min)
concmix=instantaneous concentration of the tracer gas after mixing, (ppm)
ρEXH=density of the exhaust gas (kg/m3)
conca=background concentration of the tracer gas in the intake air (ppm)

The background concentration of the tracer gas (conc a) may be determined by averaging the background concentration measured immediately before and after the test run.

When the background concentration is less than 1% of the concentration of the tracer gas after mixing (conc mix.) at maximum exhaust flow, the background concentration may be neglected.

The total system shall meet the accuracy specifications for the exhaust gas flow and shall be calibrated according to Appendix 2, Section 1.11.2

1.2.5.   Air flow and air to fuel ratio measurement method

This method involves exhaust mass calculation from the air flow and the air to fuel ratio. The calculation of the instantaneous exhaust gas mass flow is as follows:



with A / F st = 14,5



where

A/Fst= stoichiometric air/fuel ratio (kg/kg)

λ= relative air /fuel ratio

concCO2 = dry CO2 concentration (%)

concCO = dry CO concentration (ppm)

concHC = HC concentration (ppm)

NOTE: The calculation refers to a diesel fuel with a H/C ratio equal to 1.8.

The air flowmeter shall meet the accuracy specifications in Table 3, the CO2 analyzer used shall meet the specifications of clause 1.4.1, and the total system shall meet the accuracy specifications for the exhaust gas flow.

Optionally, air to fuel ratio measurement equipment, such as a zirconia type sensor, may be used for the measurement of the relative air to fuel ratio in accordance with the specifications of clause 1.4.4.

1.2.6.   Total dilute exhaust gas flow

When using a full flow dilution system, the total flow of the dilute exhaust (GTOTW) shall be measured with a PDP or CFV or SSV (Annex VI, Section 1.2.1.2.) The accuracy shall conform to the provisions of Annex III, Appendix 2, Section 2.2.

1.3.   Accuracy

The calibration of all measurement instruments shall be traceable to national or international standards and comply with the requirements listed in Table 3.

Table 3. Accuracy of Measuring Instruments

No.Measuring InstrumentAccuracy
1Engine speed± 2% of reading or ± 1% of engine's max. value whichever is larger
2Torque± 2% of reading or ± 1% of engine's max. value whichever is larger
3Fuel consumption± 2% of engine's max. value
4Air consumption± 2% of reading or ± 1% of engine's max. value whichever is larger
5Exhaust gas flow± 2,5% of reading or ± 1,5% of engine's max. value whichever is larger
6Temperatures ≤ 600 K+ 2 K absolute
7Temperatures > 600 K± 1% of reading
8Exhaust gas pressure± 0,2 kPa absolute
9Intake air depression± 0,05 kPa absolute
10Atmospheric pressure± 0,1 kPa absolute
11Other pressures± 0,1 kPa absolute
12Absolute humidity± 5% of reading
13Dilution air flow± 2% of reading
14Diluted exhaust gas flow± 2% of reading

1.4.   Determination of the gaseous components

1.4.1.   General analyser specifications

The analysers shall have a measuring range appropriate for the accuracy required to measure the concentrations of the exhaust gas components (section 1.4.1.1). It is recommended that the analysers be operated in such a way that the measured concentration falls between 15% and 100% of full scale.

If the full scale value is 155 ppm (or ppm C) or less or if read-out systems (computers, data loggers) that provide sufficient accuracy and resolution below 15% of full scale are used, concentrations below 15% of full scale are also acceptable. In this case, additional calibrations are to be made to ensure the accuracy of the calibration curves - Annex III, Appendix 2, section 1.5.5.2.

The electromagnetic compatibility (EMC) of the equipment shall be on a level as to minimize additional errors.

1.4.1.1.   Measurement error

The analyzer shall not deviate from the nominal calibration point by more than ± 2% of the reading or ± 0.3% of full scale, whichever is larger.

NOTE: For the purpose of this standard, accuracy is defined as the deviation of the analyzer reading from the nominal calibration values using a calibration gas (≡ true value)

1.4.1.2.   Repeatability

The repeatability, defined as 2,5 times the standard deviation of 10 repetitive responses to a given calibration or span gas, must be no greater than ± 1% of full scale concentration for each range used above 155 ppm (or ppm C) or ± 2% of each range used below 155 ppm (or ppm C).

1.4.1.3.   Noise

The analyser peak-to-peak response to zero and calibration or span gases over any 10-second period shall not exceed 2% of full scale on all ranges used.

1.4.1.4.   Zero drift

The zero drift during a one-hour period shall be less than 2% of full scale on the lowest range used. The zero response is defined as the mean response, including noise, to a zero gas during a 30-second time interval.

1.4.1.5.   Span drift

The span drift during a one-hour period shall be less than 2% of full scale on the lowest range used. Span is defined as the difference between the span response and the zero response. The span response is defined as the mean response, including noise, to a span gas during a 30-second time interval.

1.4.2.   Gas drying

The optional gas drying device must have a minimal effect on the concentration of the measured gases. Chemical dryers are not an acceptable method of removing water from the sample.

1.4.3.   Analysers

Sections 1.4.3.1 to 1.4.3.5 of this Appendix describe the measurement principles to be used. A detailed description of the measurement systems is given in Annex VI.

The gases to be measured shall be analysed with the following instruments. For non-linear analysers, the use of linearizing circuits is permitted.

1.4.3.1.   Carbon monoxide (CO) analysis

The carbon monoxide analyser shall be of the non-dispersive infra-red (NDIR) absorption type.

1.4.3.2.   Carbon dioxide (CO2) analysis

The carbon dioxide analyser shall be of the non-dispersive infra-red (NDIR) absorption type.

1.4.3.3.   Hydrocarbon (HC) analysis

The hydrocarbon analyser shall be of the heated flame ionization detector (HFID) type with detector, valves, pipework, etc, heated so as to maintain a gas temperature of 463 K (190oC) ± 10 K.

1.4.3.4.   Oxides of nitrogen (NOx) analysis

The oxides of nitrogen analyser shall be of the chemiluminescent detector (CLD) or heated chemiluminescent detector (HCLD) type with a NO2/NO converter, if measured on a dry basis. If measured on a wet basis, a HCLD with converter maintained above 328 K (55oC) shall be used, provided the water quench check (Annex III, Appendix 2, section 1.9.2.2) is satisfied.

For both CLD and HCLD, the sampling path shall be maintained at a wall temperature of 328 K to 473 K ( 55oC to 200oC) up to the converter for dry measurement, and up to the analyzer for wet measurement.

1.4.4.   Air to fuel measurement

The air to fuel measurement equipment used to determine the exhaust gas flow as specified in section 1.2.5 shall be a wide range air to fuel ratio sensor or lambda sensor of Zirconia type.

The sensor shall be mounted directly on the exhaust pipe where the exhaust gas temperature is high enough to eliminate water condensation.

The accuracy of the sensor with incorporated electronics shall be within:

± 3% of readingλ < 2
± 5% of reading2 ≤ λ< 5
± 10% of reading5 ≤ λ

To fulfil the accuracy specified above, the sensor shall be calibrated as specified by the instrument manufacturer.

1.4.5.   Sampling for gaseous emissions

The gaseous emissions sampling probes must be fitted at least 0,5 m or three times the diameter of the exhaust pipe - whichever is the larger - upstream of the exit of the exhaust gas system as far as applicable and sufficiently close to the engine as to ensure an exhaust gas temperature of at least 343 K (70oC) at the probe.

In the case of a multi-cylinder engine with a branched exhaust manifold, the inlet of the probe shall be located sufficiently far downstream so as to ensure that the sample is representative of the average exhaust emissions from all cylinders. In multi-cylinder engines having distinct groups of manifolds, such as in a ‧V‧-engine configuration, it is permissible to acquire a sample from each group individually and calculate an average exhaust emission. Other methods which have been shown to correlate with the above methods may be used. For exhaust emissions calculation the total exhaust mass flow of the engine must be used.

If the composition of the exhaust gas is influenced by any exhaust after-treatment system, the exhaust sample must be taken upstream of this device in the tests of stage I and downstream of this device in the tests of stage II. When a full flow dilution system is used for the determination of the particulates, the gaseous emissions may also be determined in the diluted exhaust gas. The sampling probes shall be close to the particulate sampling probe in the dilution tunnel (Annex VI, section 1.2.1.2, DT and Section 1.2.2, PSP). CO and CO2 may optionally be determined by sampling into a bag and subsequent measurement of the concentration in the sampling bag.

1.5.   Determination of the particulates

The determination of the particulates requires a dilution system. Dilution may be accomplished by a partial flow dilution system or a full flow dilution system. The flow capacity of the dilution system shall be large enough to completely eliminate water condensation in the dilution and sampling systems, and maintain the temperature of the diluted exhaust gas between 315 K (42oC) and 325 K (52oC) immediately upstream of the filter holders. De-humidifying the dilution air before entering the dilution system is permitted, if the air humidity is high. Dilution air pre-heating above the temperature limit of 303 K (30 oC) is recommended, if the ambient temperature is below 293 K (20oC). However, the diluted air temperature must not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel.

NOTE: For steady-state procedure, the filter temperature may be kept at or below the maximum temperature of 325 K (52oC) instead of respecting the temperature range of 42oC - 52oC.

For a partial flow dilution system, the particulate sampling probe must be fitted close to and upstream of the gaseous probe as defined in Section 4.4 and in accordance with Annex VI, section 1.2.1.1, figure 4-12 EP and SP.

The partial flow dilution system has to be designed to split the exhaust stream into two fractions, the smaller one being diluted with air and subsequently used for particulate measurement. From that it is essential that the dilution ratio be determined very accurately. Different splitting methods can be applied, whereby the type of splitting used dictates to a significant degree the sampling hardware and procedures to be used (Annex VI, section 1.2.1.1).

To determine the mass of the particulates, a particulate sampling system, particulate sampling filters, a microgram balance and a temperature and humidity controlled weighing chamber are required.

For particulate sampling, two methods may be applied:

the single filter method uses one pair of filters (1.5.1.3. of this Appendix) for all modes of the test cycle. Considerable attention must be paid to sampling times and flows during the sampling phase of the test. However, only one pair of filters will be required for the test cycle,

the multiple filter method dictates that one pair of filters (section 1.5.1.3. of this Appendix) is used for each of the individual modes of the test cycle. This method allows more lenient sample procedures but uses more filters.

1.5.1.   Particulate sampling filters

1.5.1.1.   Filter specification

Fluorocarbon coated glass fibre filters or fluorocarbon based membrane filters are required for certification tests. For special applications different filter materials may be used. All filter types shall have a 0,3 µm DOP (di-octylphthalate) collection efficiency of at least 99% at a gas face velocity between 35 and 100 cm/s. When performing correlation tests between laboratories or between a manufacturer and an approval authority, filters of identical quality must be used.

1.5.1.2.   Filter size

Particulate filters must have a minimum diameter of 47 mm (37 mm stain diameter). Larger diameter filters are acceptable (section 1.5.1.5.).

1.5.1.3.   Primary and back-up filters

The diluted exhaust shall be sampled by a pair of filters placed in series (one primary and one back-up filter) during the test sequence. The back-up filter shall be located no more than 100 mm downstream of, and shall not be in contact with, the primary filter. The filters may be weighed separately or as a pair with the filters placed stain side to stain side.

1.5.1.4.   Filter face velocity

A gas face velocity through the filter of 35 to 100 cm/s shall be achieved. The pressure drop increase between the beginning and the end of the test shall be no more than 25 kPa.

1.5.1.5.   Filter loading

The recommended minimum filter loadings for the most common filter sizes are shown in the following table. For larger filter sizes, the minimum filter loading shall be 0,065 mg/1000 mm2 filter area.

Filter Diameter (mm)Recommended stain diameter (mm)Recommended minimum loading (mg)
47370,11
70600,25
90800,41
1101000,62

For the multiple filter method, the recommended minimum filter loading for the sum of all filters shall be the product of the appropriate value above and the square root of the total number of modes.

1.5.2.   Weighing chamber and analytical balance specifications

1.5.2.1.   Weighing chamber conditions

The temperature of the chamber (or room) in which the particulate filters are conditioned and weighed shall be maintained to within 295 K (22oC) ± 3K during all filter conditioning and weighing. The humidity shall be maintained to a dew point of 282,5 (9,5oC) ± 3K and a relative humidity of 45 ± 8%.

1.5.2.2.   Reference filter weighing

The chamber (or room) environment shall be free of any ambient contaminants (such as dust) that would settle on the particulate filters during their stabilisation. Disturbances to weighing room specifications as outlined in section 1.5.2.1 will be allowed if the duration of the disturbances does not exceed 30 minutes. The weighing room should meet the required specifications prior to personnel entrance into the weighing room. At least two unused reference filters or reference filter pairs shall be weighed within four hours of, but preferably at the same time as the sample filter (pair) weighing. They shall be the same size and material as the sample filters.

If the average weight of the reference filters (reference filter pairs) changes between sample filter weighing by more than 10 μg, then all sample filters shall be discarded and the emissions test repeated.

If the weighing room stability criteria outlined in section 1.5.2.1 is not met, but the reference filter (pair) weighing meet the above criteria, the engine manufacturer has the option of accepting the sample filter weights or voiding the tests, fixing the weighing room control system and re-running the test.

1.5.2.3.   Analytical balance

The analytical balance used to determine the weights of all filters shall have a precision (standard deviation) of 2 (μg and a resolution of 1 μg (1 digit = 1 μg) specified by the balance manufacturer.

1.5.2.4.   Elimination of static electricity effects

To eliminate the effects of static electricity, the filters shall be neutralized prior to weighing, for example, by a Polonium neutralizer or a device of similar effect.

1.5.3.   Additional specifications for particulate measurement

All parts of the dilution system and the sampling system from the exhaust pipe up to the filter holder, which are in contact with raw and diluted exhaust gas, must be designed to minimize deposition or alteration of the particulates. All parts must be made of electrically conductive materials that do not react with exhaust gas components, and must be electrically grounded to prevent electrostatic effects.

2. MEASUREMENT AND SAMPLING PROCEDURES (NRTC TEST)

2.1.   Introduction

Gaseous and particulate components emitted by the engine submitted for testing shall be measured by the methods of Annex VI. The methods of Annex VI describe the recommended analytical systems for the gaseous emissions (Section 1.1) and the recommended particulate dilution and sampling systems (Section 1.2).

2.2.   Dynamometer and test cell equipment

The following equipment shall be used for emission tests of engines on engine dynamometers:

2.2.1.   Engine Dynamometer

An engine dynamometer shall be used with adequate characteristics to perform the test cycle described in Appendix 4 to this Annex. The instrumentation for torque and speed measurement shall allow the measurement of the power within the given limits. Additional calculations may be necessary. The accuracy of the measuring equipment must be such that the maximum tolerances of the figures given in Table 3 are not exceeded.

2.2.2.   Other Instruments

Measuring instruments for fuel consumption, air consumption, temperature of coolant and lubricant, exhaust gas pressure and intake manifold depression, exhaust gas temperature, air intake temperature, atmospheric pressure, humidity and fuel temperature shall be used, as required. These instruments shall satisfy the requirements given in Table 3:

Table 3. Accuracy of Measuring Instruments

No.Measuring InstrumentAccuracy
1Engine speed± 2% of reading or ± 1% of engine's max. value, whichever is larger
2Torque± 2% of reading or ± 1% of engine's max. value, whichever is larger
3Fuel consumption± 2% of engine's max. value
4Air consumption± 2% of reading or ± 1% of engine's max. value, whichever is larger
5Exhaust gas flow± 2,5% of reading or ± 1,5% of engine's max. value, whichever is larger
6Temperatures ≤ 600 K+ 2K absolute
7Temperatures > 600 K± 1% of reading
8Exhaust gas pressure± 0,2 kPa absolute
9Intake air depression± 0,05 kPa absolute
10Atmospheric pressure± 0,1 kPa absolute
11Other pressures± 0,1 kPa absolute
12Absolute humidity± 5% of reading
13Dilution air flow± 2% of reading
14Diluted exhaust gas flow± 2% of reading

2.2.3.   Raw Exhaust Gas Flow

For calculating the emissions in the raw exhaust gas and for controlling a partial flow dilution system, it is necessary to know the exhaust gas mass flow rate. For determinating the exhaust mass flow rate, either of the methods described below may be used.

For the purpose of emissions calculation, the response time of either method described below shall be equal to or less than the requirement for the analyzer response time, as defined in Appendix 2, Section 1.11.1.

For the purpose of controlling a partial flow dilution system, a faster response is required. For partial flow dilution systems with online control, a response time of ≤ 0,3 s is required. For partial flow dilution systems with look ahead control based on a pre-recorded test run, a response time of the exhaust flow measurement system of ≤ 5 s with a rise time of ≤ 1 s is required. The system response time shall be specified by the instrument manufacturer. The combined response time requirements for exhaust gas flow and partial flow dilution system are indicated in Section 2.4.

Direct measurement method

Direct measurement of the instantaneous exhaust flow may be done by systems, such as:

pressure differential devices, like flow nozzle, (for details see ISO 5167: 2000)

ultrasonic flowmeter

vortex flowmeter.

Precautions shall be taken to avoid measurement errors, which will impact emission value errors. Such precautions include the careful installation of the device in the engine exhaust system according to the instrument manufacturers' recommendations and to good engineering practice. Especially, engine performance and emissions must not be affected by the installation of the device.

The flowmeters shall meet the accuracy specifications of Table 3.

Air and fuel measurement method

This involves measurement of the airflow and the fuel flow with suitable flowmeters. The calculation of the instantaneous exhaust gas flow is as follows:

G EXHW = G AIRW + G FUEL (for wet exhaust mass)

The flowmeters shall meet the accuracy specifications of Table 3, but shall also be accurate enough to also meet the accuracy specifications for the exhaust gas flow.

Tracer measurement method

This involves measurement of the concentration of a tracer gas in the exhaust.

A known amount of an inert gas (e.g. pure helium) shall be injected into the exhaust gas flow as a tracer. The gas is mixed and diluted by the exhaust gas, but must not react in the exhaust pipe. The concentration of the gas shall then be measured in the exhaust gas sample.

In order to ensure complete mixing of the tracer gas, the exhaust gas sampling probe shall be located at least 1 m or 30 times the diameter of the exhaust pipe, whichever is larger, downstream of the tracer gas injection point. The sampling probe may be located closer to the injection point if complete mixing is verified by comparing the tracer gas concentration with the reference concentration when the tracer gas is injected upstream of the engine.

The tracer gas flow rate shall be set so that the tracer gas concentration at engine idle speed after mixing becomes lower than the full scale of the trace gas analyzer.

The calculation of the exhaust gas flow is as follows:



where

G EXHW = instantaneous exhaust mass flow (kg/s)

G T = tracer gas flow (cm3/min)

conc mix = instantaneous concentration of the tracer gas after mixing (ppm)

ρ EXH = density of the exhaust gas (kg/m3)

conc a = background concentration of the tracer gas in the intake air (ppm)

The background concentration of the tracer gas (conc a) may be determined by averaging the background concentration measured immediately before the test run and after the test run.

When the background concentration is less than 1% of the concentration of the tracer gas after mixing (conc mix.) at maximum exhaust flow, the background concentration may be neglected.

The total system shall meet the accuracy specifications for the exhaust gas flow, and shall be calibrated according to Appendix 2, paragraph 1.11.2

Air flow and air to fuel ratio measurement method

This involves exhaust mass calculation from the airflow and the air to fuel ratio. The calculation of the instantaneous exhaust gas mass flow is as follows:



with A / F st = 14,5



where

A/Fst= stoichiometric air/fuel ratio (kg/kg)

λ= relative air /fuel ratio

concCO2 = dry CO2 concentration (%)

concCO = dry CO concentration (ppm)

concHC = HC concentration (ppm)

NOTE: The calculation refers to a diesel fuel with a H/C ratio equal to 1.8.

The air flowmeter shall meet the accuracy specifications in Table 3, the CO2 analyzer used shall meet the specifications of section 2.3.1, and the total system shall meet the accuracy specifications for the exhaust gas flow.

Optionally, air to fuel ratio measurement equipment, such as a zirconia type sensor, may be used for the measurement of the excess air ratio in accordance with the specifications of section 2.3.4.

2.2.4.   Diluted Exhaust Gas Flow

For calculation of the emissions in the diluted exhaust gas, it is necessary to know the diluted exhaust gas mass flow rate. The total diluted exhaust gas flow over the cycle (kg/test) shall be calculated from the measurement values over the cycle and the corresponding calibration data of the flow measurement device (V 0 for PDP, K V for CFV, C d for SSV): the corresponding methods described in Appendix 3, section 2.2.1 shall be used. If the total sample mass of particulates and gaseous pollutants exceeds 0,5% of the total CVS flow, the CVS flow shall be corrected or the particulate sample flow shall be returned to the CVS prior to the flow measuring device.

2.3.   Determination of the gaseous components

2.3.1.   General Analyser Specifications

The analysers shall have a measuring range appropriate for the accuracy required to measure the concentrations of the exhaust gas components (section 1.4.1.1). It is recommended that the analysers be operated in such a way that the measured concentration falls between 15% and 100% of full scale.

If the full scale value is 155 ppm (or ppm C) or less, or if read-out systems (computers, data loggers) that provide sufficient accuracy and resolution below 15% of full scale are used, concentrations below 15% of full scale are also acceptable. In this case, additional calibrations are to be made to ensure the accuracy of the calibration curves - Annex III, Appendix 2, section 1.5.5.2.

The electromagnetic compatibility (EMC) of the equipment shall be of a level such as to minimize additional errors.

2.3.1.1.   Measurement error

The analyzer shall not deviate from the nominal calibration point by more than ± 2% of the reading or ± 0,3% of full scale, whichever is larger.

NOTE: For the purpose of this standard, accuracy is defined as the deviation of the analyzer reading from the nominal calibration values using a calibration gas (≡ true value).

2.3.1.2.   Repeatability

The repeatability, defined as 2,5 times the standard deviation of 10 repetitive responses to a given calibration or span gas, must be no greater than ± 1% of full scale concentration for each range used above 155 ppm (or ppm C) or ± 2% for each range used below 155 ppm (or ppm C).

2.3.1.3.   Noise

The analyser peak-to-peak response to zero and calibration or span gases over any 10-second period shall not exceed 2% of full scale on all ranges used.

2.3.1.4.   Zero drift

The zero drift during a one-hour period shall be less than 2% of full scale on the lowest range used. The zero response is defined as the mean response, including noise, to a zero gas during a 30-second time interval.

2.3.1.5.   Span drift

The span drift during a one-hour period shall be less than 2% of full scale on the lowest range used. Span is defined as the difference between the span response and the zero response. The span response is defined as the mean response, including noise, to a span gas during a 30-second time interval.

2.3.1.6.   Rise Time

For raw exhaust gas analysis, the rise time of the analyzer installed in the measurement system shall not exceed 2,5 s.

NOTE: Only evaluating the response time of the analyzer alone will not clearly define the suitability of the total system for transient testing. Volumes, and especially dead volumes, through out the system will not only affect the transportation time from the probe to the analyzer, but also affect the rise time. Also transport times inside of an analyzer would be defined as analyzer response time, like the converter or water traps inside of a NOx analyzers. The determination of the total system response time is described in Appendix 2, Section 1.11.1.

2.3.2.   Gas Drying

Same specifications as for NRSC test cycle apply (Section 1.4.2) as described here below.

The optional gas drying device must have a minimal effect on the concentration of the measured gases. Chemical dryers are not an acceptable method of removing water from the sample.

2.3.3.   Analysers

Same specifications as for NRSC test cycle apply (Section 1.4.3) as described here below.

The gases to be measured shall be analysed with the following instruments. For non-linear analysers, the use of linearizing circuits is permitted.

2.3.3.1.   Carbon monoxide (CO) analysis

The carbon monoxide analyser shall be of the non-dispersive infra-red (NDIR) absorption type.

2.3.3.2.   Carbon dioxide (CO2) analysis

The carbon dioxide analyser shall be of the non-dispersive infra-red (NDIR) absorption type.

2.3.3.3.   Hydrocarbon (HC) analysis

The hydrocarbon analyser shall be of the heated flame ionization detector (HFID) type with detector, valves, pipework, etc, heated so as to maintain a gas temperature of 463 K (190oC) ± 10 K.

2.3.3.4.   Oxides of nitrogen (NOx) analysis

The oxides of nitrogen analyser shall be of the chemiluminescent detector (CLD) or heated chemiluminescent detector (HCLD) type with a NO2/NO converter, if measured on a dry basis. If measured on a wet basis, a HCLD with converter maintained above 328 K (55oC shall be used, provided the water quench check (Annex III, Appendix 2, section 1.9.2.2) is satisfied.

For both CLD and HCLD, the sampling path shall be maintained at a wall temperature of 328 K to 473 K ( 55oC to 200oC) up to the converter for dry measurement, and up to the analyzer for wet measurement.

2.3.4.   Air to fuel measurement

The air to fuel measurement equipment used to determine the exhaust gas flow as specified in section 2.2.3 shall be a wide range air to fuel ratio sensor or lambda sensor of Zirconia type.

The sensor shall be mounted directly on the exhaust pipe where the exhaust gas temperature is high enough to eliminate water condensation.

The accuracy of the sensor with incorporated electronics shall be within:

± 3 % of readingλ < 2
± 5 % of reading2 ≤λ < 5
± 10% of reading5 ≤ λ

To fulfil the accuracy specified above, the sensor shall be calibrated as specified by the instrument manufacturer.

2.3.5.   Sampling of Gaseous Emissions

2.3.5.1.   Raw exhaust gas flow

For calculation of the emissions in the raw exhaust gas the same specifications as for NRSC test cycle apply (Section 1.4.4), as described here below.

The gaseous emissions sampling probes must be fitted at least 0,5 m or three times the diameter of the exhaust pipe -whichever is the larger - upstream of the exit of the exhaust gas system as far as applicable and sufficiently close to the engine as to ensure an exhaust gas temperature of at least 343 K (70oC) at the probe.

In the case of a multicylinder engine with a branched exhaust manifold, the inlet of the probe shall be located sufficiently far downstream so as to ensure that the sample is representative of the average exhaust emissions from all cylinders. In multicylinder engines having distinct groups of manifolds, such as in a ‧V‧-engine configuration, it is permissible to acquire a sample from each group individually and calculate an average exhaust emission. Other methods which have been shown to correlate with the above methods may be used. For exhaust emissions calculation the total exhaust mass flow of the engine must be used.

If the composition of the exhaust gas is influenced by any exhaust after-treatment system, the exhaust sample must be taken upstream of this device in the tests of stage I and downstream of this device in the tests of stage II.

2.3.5.2.   Diluted exhaust gas flow

If a full flow dilution system is used, the following specifications apply.

The exhaust pipe between the engine and the full flow dilution system shall conform to the requirements of Annex VI.

The gaseous emissions sample probe(s) shall be installed in the dilution tunnel at a point where the dilution air and exhaust gas are well mixed, and in close proximity to the particulates sampling probe.

Sampling can generally be done in two ways:

the pollutants are sampled into a sampling bag over the cycle and measured after completion of the test;

the pollutants are sampled continuously and integrated over the cycle; this method is mandatory for HC and NOx.

The background concentrations shall be sampled upstream of the dilution tunnel into a sampling bag, and shall be subtracted from the emissions concentration according to Appendix 3, Section 2.2.3.

2.4.   Determination of the participates

Determination of the particulates requires a dilution system. Dilution may be accomplished by a partial flow dilution system or a full flow dilution system. The flow capacity of the dilution system shall be large enough to completely eliminate water condensation in the dilution and sampling systems, and maintain the temperature of the diluted exhaust gas between 315 K (42oC) and 325 K (52oC) immediately upstream of the filter holders. De-humidifying the dilution air before entering the dilution system is permitted, if the air humidity is high. Dilution air pre-heating above the temperature limit of 303 K (30 oC) is recommended if the ambient temperature is below 293 K (20 C). However, the diluted air temperature must not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel.

The particulate sampling probe shall be installed in close proximity to the gaseous emissions sampling probe, and the installation shall comply with the provisions of Section 2.3.5.

To determine the mass of the particulates, a particulate sampling system, particulate sampling filters, microgram balance, and a temperature and humidity controlled weighing chamber, are required.

Partial flow dilution system specifications

The partial flow dilution system has to be designed to split the exhaust stream into two fractions, the smaller one being diluted with air and subsequently used for particulate measurement. For this it is essential that the dilution ratio be determined very accurately. Different splitting methods can be applied, whereby the type of splitting used dictates to a significant degree the sampling hardware and procedures to be used (Annex VI, section 1.2.1.1).

For the control of a partial flow dilution system, a fast system response is required. The transformation time for the system shall be determined by the procedure described in Appendix 2, Section 1.11.1.

If the combined transformation time of the exhaust flow measurement (see previous Section) and the partial flow system is less than 0,3 s, online control may be used. If the transformation time exceeds 0,3 s, look ahead control based on a pre-recorded test run must be used. In this case, the rise time shall be ≤ 1 s and the delay time of the combination ≤ 10 s.

The total system response shall be designed as to ensure a representative sample of the particulates, G SE , proportional to the exhaust mass flow. To determine the proportionality, a regression analysis of G SE versus G EXHW shall be conducted on a minimum 5 Hz data acquisition rate, and the following criteria shall be met:

The correlation coefficient r2 of the linear regression between GSE and GEXHW shall be not less than 0,95.

The standard error of estimate of GSE on GEXHW shall not exceed 5% of GSE maximum.

GSE intercept of the regression line shall not exceed ± 2% of GSE maximum.

Optionally, a pre-test may be run, and the exhaust mass flow signal of the pre-test be used for controlling the sample flow into the particulate system ("look-ahead control"). Such a procedure is required if the transformation time of the particulate system, t 50,P or/and the transformation time of the exhaust mass flow signal, t 50,F are > 0,3 s. A correct control of the partial dilution system is obtained, if the time trace of G EXHW,pre of the pre-test, which controls G SE , is shifted by a "look-ahead" time of t 50,P + t 50,F.

For establishing the correlation between G SE and G EXHW the data taken during the actual test shall be used, with G EXHW time aligned by t50,F relative to G SE (no contribution from t 50,P to the time alignment). That is, the time shift between G EXHW and G SE is the difference in their transformation times that were determined in Appendix 2, Section 2.6.

For partial flow dilution systems, the accuracy of the sample flow G SE is of special concern, if not measured directly, but determined by differential flow measurement:

G SE = G TOTW - G DILW

In this case an accuracy of ± 2% for G TOTW and G DILW is not sufficient to guarantee acceptable accuracies of G SE . If the gas flow is determined by differential flow measurement, the maximum error of the difference shall be such that the accuracy of G SE is within ± 5% when the dilution ratio is less than 15. It can be calculated by taking root-mean-square of the errors of each instrument.

Acceptable accuracies of G SE can be obtained by either of the following methods:

(a)The absolute accuracies of GTOTW and GDILW are ± 0,2% which guarantees an accuracy of GSE of ≤ 5% at a dilution ratio of 15. However, greater errors will occur at higher dilution ratios.

(b)Calibration of GDILW relative to GTOTW is carried out such that the same accuracies for GSE as in (a) are obtained. For the details of such a calibration see Appendix 2, Section 2.6.

(c)The accuracy of GSE is determined indirectly from the accuracy of the dilution ratio as determined by a tracer gas, e.g. CO2. Again, accuracies equivalent to method (a) for GSE are required.

(d)The absolute accuracy of GTOTW and GDILW is within ± 2% of full scale, the maximum error of the difference between GTOTW and GDILW is within 0,2%, and the linearity error is within ± 0.2% of the highest GTOTW observed during the test.

2.4.1.   Particulate Sampling Filters

2.4.1.1.   Filter specification

Fluorocarbon coated glass fibre filters or fluorocarbon based membrane filters are required for certification tests. For special applications different filter materials may be used. All filter types shall have a 0,3 µm DOP (di-octylphthalate) collection efficiency of at least 99% at a gas face velocity between 35 and 100 cm/s. When performing correlation tests between laboratories or between a manufacturer and an approval authority, filters of identical quality must be used.

2.4.1.2.   Filter size

Particulate filters must have a minimum diameter of 47 mm (37 mm stain diameter). Larger diameter filters are acceptable (section 2.4.1.5.).

2.4.1.3.   Primary and back-up filters

The diluted exhaust shall be sampled by a pair of filters placed in series (one primary and one back-up filter) during the test sequence. The back-up filter shall be located no more than 100 mm downstream of, and shall not be in contact with, the primary filter. The filters may be weighed separately or as a pair with the filters placed stain side to stain side.

2.4.1.4.   Filter face velocity

A gas face velocity through the filter of 35 to 100 cm/s shall be achieved. The pressure drop increase between the beginning and the end of the test shall be no more than 25 kPa.

2.4.1.5.   Filter loading

The recommended minimum filter loadings for the most common filter sizes are shown in the following table. For larger filter sizes, the minimum filter loading shall be 0,065 mg/1000 mm2 filter area.

Filter Diameter (mm)Recommended stain diameter (mm)Recommended minimum loading (mg)
47370,11
70600,25
90800,41
1101000,62

2.4.2.   Weighing Chamber and Analytical Balance Specifications

2.4.2.1.   Weighing chamber conditions

The temperature of the chamber (or room) in which the particulate filters are conditioned and weighed shall be maintained to within 295 K (22oC) ±3K during all filter conditioning and weighing. The humidity shall be maintained to a dewpoint of 282,5 (9,5oC) ± 3 K and a relative humidity of 45 ± 8%.

2.4.2.2.   Reference filter weighing

The chamber (or room) environment shall be free of any ambient contaminants (such as dust) that would settle on the particulate filters during their stabilisation. Disturbances to weighing room specifications as outlined in section 2.4.2.1 will be allowed if the duration of the disturbances does not exceed 30 minutes. The weighing room should meet the required specifications prior to personnel entrance into the weighing room. At least two unused reference filters or reference filter pairs shall be weighed within four hours of, but preferably at the same time as the sample filter (pair) weighing. They shall be the same size and material as the sample filters.

If the average weight of the reference filters (reference filter pairs) changes between sample filter weighing by more than 10µg, then all sample filters shall be discarded and the emissions test repeated.

If the weighing room stability criteria outlined in section 2.4.2.1 are not met, but the reference filter (pair) weighing meet the above criteria, the engine manufacturer has the option of accepting the sample filter weights or voiding the tests, fixing the weighing room control system and re-running the test.

2.4.2.3.   Analytical balance

The analytical balance used to determine the weights of all filters shall have a precision (standard deviation) of 2 (µg and a resolution of 1 µg (1 digit = 1 µg) specified by the balance manufacturer.

2.4.2.4.   Elimination of static electricity effects

To eliminate the effects of static electricity, the filters shall be neutralized prior to weighing, for example, by a Polonium neutralizer or a device having similar effect.

2.4.3.   Additional Specifications for Particulate Measurement

All parts of the dilution system and the sampling system from the exhaust pipe up to the filter holder, which are in contact with raw and diluted exhaust gas, must be designed to minimize deposition or alteration of the particulates. All parts must be made of electrically conductive materials that do not react with exhaust gas components, and must be electrically grounded to prevent electrostatic effects.”

6)Appendix 2 shall be amended as follows:

(a)The title shall be amended as follows:

"APPENDIX 2

CALIBRATION PROCEDURE (NRSC, NRTC (7))"

(b)Section 1.2.2 shall be amended as follows:

After the current text the following shall be added:

"This accuracy implies that primary gases used for blending shall be known to have an accuracy of at least ± 1%, traceable to national or international gas standards. The verification shall be performed at between 15 and 50% of full scale for each calibration incorporating a blending device. An additional verification may be performed using another calibration gas, if the first verification has failed.

Optionally, the blending device may be checked with an instrument which by nature is linear, e.g. using NO gas with a CLD. The span value of the instrument shall be adjusted with the span gas directly connected to the instrument. The blending device shall be checked at the used settings and the nominal value shall be compared to the measured concentration of the instrument. This difference shall in each point be within ± 1% of the nominal value.

Other methods may be used based on good engineering practice and with the prior agreement of the parties involved.

NOTE: A precision gas divider of accuracy is within ± 1%, is recommended for establishing the accurate analyzer calibration curve. The gas divider shall be calibrated by the instrument manufacturer."

(c)section 1.5.5.1 shall be amended as follows:

(i)the first sentence shall be replaced by the following:

"The analyser calibration curve is established by at least six calibration points (excluding zero) spaced as uniformly as possible".

(ii)the third indent shall be replaced by the following:

"The calibration curve must not differ by more than ± 2% from the nominal value of each calibration point and by more than ±0,3% of full scale at zero."

(d)in section 1.5.5.2, the last indent shall be replaced by the following:

"The calibration curve must not differ by more than ± 4% from the nominal value of each calibration point and by more than ± 0,3% of full scale at zero."

(e)the text under section 1.8.3 shall be replaced by the following:

"The oxygen interference check shall be determined when introducing an analyser into service and after major service intervals.

A range shall be chosen where the oxygen interference check gases will fall within the upper 50%. The test shall be conducted with the oven temperature set as required.

1.8.3.1.   Oxygen interference gases

Oxygen interference check gases shall contain propane with 350 ppmC ÷ 75 ppmC hydrocarbon. The concentration value shall be determined to calibration gas tolerances by chromatographic analysis of total hydrocarbons plus impurities or by dynamic blending. Nitrogen shall be the predominant diluent with the balance oxygen. Blends required for Diesel engine testing are:

O2 concentrationBalance
21 (20 to 22)Nitrogen
10 (9 to 11Nitrogen
5 (4 to 6)Nitrogen

1.8.3.2.   Procedure

(a)The analyzer shall be zeroed.

(b)The analyzer shall be spanned with the 21% oxygen blend.

(c)The zero response shall be rechecked. If it has changed more than 0,5% of full scale clauses (a) and (b) shall be repeated.

(d)The 5% and 10% oxygen interference check gases shall be introduced.

(e)The zero response shall be rechecked. If it has changed more than ± 1 % of full scale, the test shall be repeated.

(f)The oxygen interference (%O2I) shall be calculated for each mixture in (d) as follows:


A=hydrocarbon concentration (ppmC) of the span gas used in (b)
B=hydrocarbon concentration (ppmC) of the oxygen interference check gases used in (d)
C=analyzer response


D=percent of full scale analyzer response due to A.

(g)The % of oxygen interference (%O2I) shall be less than ± 3,0% for all required oxygen interference check gases prior to testing.

(h)If the oxygen interference is greater than ± 3,0%, the air flow above and below the manufacturer's specifications shall be incrementally adjusted, repeating clause 1.8.1 for each flow.

(i)If the oxygen interference is greater than ± 3,0% after adjusting the air flow, the fuel flow and thereafter the sample flow shall be varied, repeating clause 1.8.1 for each new setting.

(j)If the oxygen interference is still greater than ± 3,0%, the analyzer, FID fuel, or burner air shall be repaired or replaced prior to testing. This clause shall then be repeated with the repaired or replaced equipment or gases."

(f)Current paragraph 1.9.2.2 shall be amended as follows:

(i)the first subparagraph shall be replaced by the following:

"This check applies to wet gas concentration measurements only. Calculation of water quench must consider dilution of the NO span gas with water vapour and scaling of water vapour concentration of the mixture to that expected during testing. A NO span gas having a concentration of 80 to 100% of full scale to the normal operating range shall be passed through the (H)CLD and the NO value recorded as D. The NO gas shall be bubbled through water at room temperature and passed through the (H)CLD and NO value recorded as C. The water temperature shall be determined and recorded as F. The mixture's saturation vapour pressure that corresponds to the bubbler water temperature (F) shall be determined and recorded as G. The water vapour concentration (in %) of the mixture shall be calculated as follows:"

(ii)The third subparagraph shall be replaced by the following:

"and recorded as De. For diesel exhaust, the maximum exhaust water vapour concentration (in %) expected during testing shall be estimated, under the assumption of a fuel atom H/C ratio of 1,8 to 1, from the maximum CO2 concentration in the exhaust gas or from the undiluted CO2 span gas concentration (A, as measured in section 1.9.2.1) as follows:

(g)the following section shall be inserted:

"1.11.   Additional calibration requirements for raw exhaust measurements over NRTC test

1.11.1.   Response time check of the analytical system

The system settings for the response time evaluation shall be exactly the same as during measurement of the test run (i.e. pressure, flow rates, filter settings on the analyzers and all other response time influences). The response time determination shall be done with gas switching directly at the inlet of the sample probe. The gas switching shall be done in less than 0,1 second. The gases used for the test shall cause a concentration change of at least 60% FS.

The concentration trace of each single gas component shall be recorded. The response time is defined as the difference in time between the gas switching and the appropriate change of the recorded concentration. The system response time (t90) consists of the delay time to the measuring detector and the rise time of the detector. The delay time is defined as the time from the change (t0) until the response is 10% of the final reading (t10). The rise time is defined as the time between 10% and 90% response of the final reading (t90 - t10).

For time alignment of the analyzer and exhaust flow signals in the case of raw measurement, the transformation time is defined as the time from the change (t0) until the response is 50% of the final reading (t50).

The system response time shall be = 10 seconds with a rise time = 2,5 seconds for all limited components (CO, NOx, HC) and all ranges used.

1.11.2.   Calibration of tracer gas analyzer for exhaust flow measurement

The analyzer for measurement of the tracer gas concentration, if used, shall be calibrated using the standard gas.

The calibration curve shall be established by at least 10 calibration points (excluding zero) spaced so that a half of the calibration points are placed between 4% to 20% of analyzer's full scale and the rest are in between 20% to 100% of the full scale. The calibration curve is calculated by the method of least squares.

The calibration curve shall not differ by more than ± 1% of the full scale from the nominal value of each calibration point, in the range from 20% to 100% of the full scale. It shall also not differ by more than ± 2% from the nominal value in the range from 4% to 20% of the full scale.

The analyzer shall be set at zero and spanned prior to the test run using a zero gas and a span gas whose nominal value is more than 80% of the analyzer full scale."

(h)paragraph 2.2 shall be replaced by the following:

"2.2.The calibration of gas flow-meters or flow measurement instrumentation shall be traceable to national and/or international standards.

The maximum error of the measured value shall be within ± 2% of reading.

For partial flow dilution systems, the accuracy of the sample flow G SE is of special concern, if not measured directly, but determined by differential flow measurement:

G SE = G TOTW - G DILW

In this case an accuracy of ± 2% for G TOTW and G DILW is not sufficient to guarantee acceptable accuracies of G SE If the gas flow is determined by differential flow measurement, the maximum error of the difference shall be such that the accuracy of G SE is within ± 5% when the dilution ratio is less than 15. It can be calculated by taking root-mean-square of the errors of each instrument."

(i)the following section shall be added:

"2.6.   Additional calibration requirements for partial flow dilution systems

2.6.1.   Periodical calibration

If the sample gas flow is determined by differential flow measurement the flow meter or the flow measurement instrumentation shall be calibrated by one of the following procedures, such that the probe flow GSE into the tunnel fulfils the accuracy requirements of Appendix I section 2.4:

The flow meter for GDILW is connected in series to the flow meter for G TOTW , the difference between the two flow meters is calibrated for at least 5 set points with flow values equally spaced between the lowest GDILW value used during the test and the value of G TOTW used during the test The dilution tunnel may be bypassed.

A calibrated mass flow device is connected in series to the flowmeter for G TOTW and the accuracy is checked for the value used for the test. Then the calibrated mass flow device is connected in series to the flow meter for GDILW, and the accuracy is checked for at least 5 settings corresponding to the dilution ratio between 3 and 50, relative to G TOTW used during the test.

The transfer tube TT is disconnected from the exhaust, and a calibrated flow measuring device with a suitable range to measure GSE is connected to the transfer tube. Then G TOTW is set to the value used during the test, and GDILW is sequentially set to at least 5 values corresponding to dilution ratios q between 3 and 50. Alternatively, a special calibration flow pathmay be provided, in which the tunnel is bypassed, but the total and dilution air flow through the corresponding meters are maintained as in the actual test.

A tracer gas is fed into the transfer tube TT. This tracer gas may be a component of the exhaust gas, like CO2 or NOx. After dilution in the tunnel the tracer gas component is measured. This shall be carried out for 5 dilution ratios between 3 and 50. The accuracy of the sample flow is determined from the dilution ration q:

GSE = G TOTW /q

The accuracies of the gas analyzers shall be taken into account to guarantee the accuracy of GSE

2.6.2.   Carbon flow check

A carbon flow check using actual exhaust is strongly recommended for detecting measurement and control problems and verifying the proper operation of the partial flow dilution system. The carbon flow check should be run at least each time a new engine is installed, or something significant is changed in the test cell configuration.

The engine shall be operated at peak torque load and speed or any other steady-state mode that produces 5% or more of CO2. The partial flow sampling system shall be operated with a dilution factor of about 15 to 1.

2.6.3.   Pre-test check

A pre-test check shall be performed within 2 hours before the test run in the following way:

The accuracy of the flow meters shall be checked by the same method as used for calibration for at least two points, including flow values of GDILW that correspond to dilution ratios between 5 and 15 for the G TOTW value used during the test.

If it can be demonstrated by records of the calibration procedure described above that the flow meter calibration is stable over a longer period of time, the pre-test check may be omitted.

2.6.4.   Determination of the transformation time

The system settings for the transformation time evaluation shall be exactly the same as during measurement of the test run. The transformation time shall be determined by the following method:

An independent reference flowmeter with a measurement range appropriate for the probe flow shall be put in series with and closely coupled to the probe. This flow meter shall have a transformation time of less than 100 ms for the flow step size used in the response time measurement, with flow restriction sufficiently low not to affect the dynamic performance of the partial flow dilution system, and consistent with good engineering practice.

A step change shall be introduced to the exhaust flow (or air flow if exhaust flow is calculated) input of the partial flow dilution system, from a low flow to at least 90% of full scale. The trigger for the step change should be the same one as that used to start the look-ahead control in actual testing. The exhaust flow step stimulus and the flowmeter response shall be recorded at a sample rate of at least 10 Hz.

From this data, the transformation time shall be determined for the partial flow dilution system, which is the time from the initiation of the step stimulus to the 50% point of the flowmeter response. In a similar manner, the transformation times of the GSE signal of the partial flow dilution system and of the G EXHW signal of the exhaust flow meter shall be determined. These signals are used in the regression checks performed after each test (Appendix I section 2.4).

The calculation shall be repeated for at least 5 rise and fall stimuli, and the results shall be averaged. The internal transformation time (<100 ms) of the reference flowmeter shall be subtracted from this value. This is the "look-ahead" value of the partial flow dilution system, which shall be applied in accordance with Appendix I section 2.4."

7)the following section shall be added:

"3.   CALIBRATION OF THE CVS SYSTEM

3.1.   General

The CVS system shall be calibrated by using an accurate flowmeter and means to change operating conditions.

The flow through the system shall be measured at different flow operating settings, and the control parameters of the system shall be measured and related to the flow.

Various type of flowmeters may be used, e.g. calibrated venturi, calibrated laminar flowmeter, calibrated turbinemeter.

3.2.   Calibration of the Positive Displacement Pump (PDP)

All the parameters related to the pump shall be simultaneously measured along with the parameters related to a calibration venturi which is connected in series with the pump. The calculated flow rate (in m3/min at pump inlet, absolute pressure and temperature) shall be plotted against a correlation function which is the value of a specific combination of pump parameters. The linear equation which relates the pump flow and the correlation function shall be determined. If a CVS has a multiple speed drive, the calibration shall be performed for each range used.

Temperature stability shall be maintained during calibration.

Leaks in all the connections and ducting between the calibration venturi and the CVS pump shall be maintained lower than 0,3% of the lowest flow point (highest restriction and lowest PDP speed point).

3.2.1.   Data Analysis

The air flowrate (Qs) at each restriction setting (minimum 6 settings) shall be calculated in standard m3/min from the flowmeter data using the manufacturer's prescribed method. The air flow rate shall then be converted to pump flow (V0) in m3/rev at absolute pump inlet temperature and pressure as follows:



where,

Qs=air flow rate at standard conditions (101,3 kPa, 273 K) (m3/s)
T=temperature at pump inlet (K)
pA=absolute pressure at pump inlet (pB- p1) (kPa)
n=pump speed (rev/s)

To account for the interaction of pressure variations at the pump and the pump slip rate, the correlation function (X0) between pump speed, pressure differential from pump inlet to pump outlet and absolute pump outlet pressure shall be calculated as follows:



where,

Δp p = pressure differential from pump inlet to pump outlet (kPa)

pA = absolute outlet pressure at pump outlet (kPa)

A linear least-square fit shall be performed to generate the calibration equation as follows:



D0 and m are the intercept and slope constants, respectively, describing the regression lines.

For a CVS system with multiple speeds, the calibration curves generated for the different pump flow ranges shall be approximately parallel, and the intercept values (D0) shall increase as the pump flow range decreases.

The values calculated by the equation shall be within ± 0,5% of the measured value of V0. Values of m will vary from one pump to another. Particulate influx over time will cause the pump slip to decrease, as reflected by lower values for m. Therefore, calibration shall be performed at pump start-up, after major maintenance, and if the total system verification (section 3.5) indicates a change in the slip rate.

3.3.   Calibration of the Critical Flow Venturi (CFV)

Calibration of the CFV is based upon the flow equation for a critical venturi. Gas flow is a function of inlet pressure and temperature, as shown below:



where,

Kv = calibration coefficient

pA = absolute pressure at venturi inlet (kPa)

T= temperature at venturi inlet (K)

3.3.1.   Data Analysis

The air flow rate (Qs) at each restriction setting (minimum 8 settings) shall be calculated in standard m3/min from the flowmeter data using the manufacturer's prescribed method. The calibration coefficient shall be calculated from the calibration data for each setting as follows:



where,

Qs = air flow rate at standard conditions (101,3 kPa, 273 K) (m3/s)

T= temperature at the venturi inlet (K)

pA = absolute pressure at venturi inlet (kPa)

To determine the range of critical flow, Kv shall be plotted as a function of venturi inlet pressure. For critical (choked) flow, Kv will have a relatively constant value. As pressure decreases (vacuum increases), the venturi becomes unchoked and Kv decreases, which indicates that the CFV is operated outside the permissible range.

For a minimum of eight points in the region of critical flow, the average KV and the standard deviation shall be calculated. The standard deviation shall not exceed ± 0,3% of the average KV

3.4.   Calibration of the Subsonic Venturi (SSV)

Calibration of the SSV is based upon the flow equation for a subsonic venturi. Gas flow is a function of inlet pressure and temperature, pressure drop between the SSV inlet and throat, as shown below:



where,

A0=collection of constants and units conversions

= 0,006111 in SI units
d=diameter of the SSV throat (m)
Cd=discharge coefficient of the SSV
PA=absolute pressure at venturi inlet (kPa)
T=temperature at the venturi inlet (K)
r=ratio of the SSV throat to inlet absolute, static pressure =
ß=ratio of the SSV throat diameter, d, to the inlet pipe inner diameter =

3.4.1.   Data Analysis

The air flow rate (QSSV) at each flow setting (minimum 16 settings) shall be calculated in standard m3/min from the flowmeter data using the manufacturer's prescribed method. The discharge coefficient shall be calculated from the calibration data for each setting as follows:



where,

QSSV=air flow rate at standard conditions (101,3 kPa, 273 K), m3/s
T=temperature at the venturi inlet, K
d=diameter of the SSV throat, m
r=ratio of the SSV throat to inlet absolute, static pressure =
ß=ratio of the SSV throat diameter, d, to the inlet pipe inner diameter =

To determine the range of subsonic flow, Cd shall be plotted as a function of Reynolds number, at the SSV throat. The Re at the SSV throat is calculated with the following formula:



where,

A1=a collection of constants and units conversions


QSSV=air flow rate at standard conditions (101,3 kPa, 273 K) (m3/s)
d=diameter of the SSV throat (m)
μ=absolute or dynamic viscosity of the gas, calculated with the following formula:



where:

b=empirical constant =
S=empirical constant = 110,4 K

Because QSSV is an input to the Re formula, the calculations must be started with an initial guess for QSSV or Cd of the calibration venturi, and repeated until QSSV converges. The convergence method must be accurate to 0,1% or better.

For a minimum of sixteen points in the subsonic flow region, the calculated values of Cd from the resulting calibration curve fit equation must be within ± 0,5% of the measured Cd for each calibration point.

3.5.   Total System Verification

The total accuracy of the CVS sampling system and analytical system shall be determined by introducing a known mass of a pollutant gas into the system while it is being operated in the normal manner. The pollutant is analysed, and the mass calculated according to Annex III, Appendix 3, section 2.4.1 except in the case of propane where a factor of 0,000472 is used in place of 0,000479 for HC. Either of the following two techniques shall be used.

3.5.1.   Metering with a Critical Flow Orifice

A known quantity of pure gas (propane) shall be fed into the CVS system through a calibrated critical orifice. If the inlet pressure is high enough, the flow rate, which is adjusted by means of the critical flow orifice, is independent of the orifice outlet pressure (critical flow). The CVS system shall be operated as in a normal exhaust emission test for about 5 to 10 minutes. A gas sample shall be analysed with the usual equipment (sampling bag or integrating method), and the mass of the gas calculated. The mass so determined shall be within ± 3% of the known mass of the gas injected.

3.5.2.   Metering by Means of a Gravimetric Technique

The weight of a small cylinder filled with propane shall be determined with a precision of ± 0,01 g. For about 5 to 10 minutes, the CVS system shall be operated as in a normal exhaust emission test, while carbon monoxide or propane is injected into the system. The quantity of pure gas discharged shall be determined by means of differential weighing. A gas sample shall be analysed with the usual equipment (sampling bag or integrating method), and the mass of the gas calculated. The mass so determined shall be within ± 3% of the known mass of the gas injected."

8)Appendix 3 shall be amended as follows:

(a)The following title for this Appendix shall be inserted: "DATA EVALUATION AND CALCULATIONS"

(b)the title of section 1 shall read "DATA EVALUATION AND CALCULATIONS - NRSC TEST"

(c)section 1.2 shall be replaced by the following:

"1.2Participate emissions

For the evaluation of the particulates, the total sample masses (MSAM,i) through the filters shall be recorded for each mode. The filters shall be returned to the weighing chamber and conditioned for at least one hour, but not more than 80 hours, and then weighed. The gross weight of the filters shall be recorded and the tare weight (see section 3.1, Annex III) subtracted. The particulate mass (Mf for single filter method; Mf,i for the multiple filter method) is the sum of the particulate masses collected on the primary and back-up filters. If background correction is to be applied, the dilution air mass (MDIL) through the filters and the particulate mass (Md) shall be recorded. If more than one measurement was made, the quotient Md/MDIL must be calculated for each single measurement and the values averaged."

(d)section 1.3.1 shall be replaced by the following:

"1.3.1.Determination of the exhaust gas flow

The exhaust gas flow rate (GEXHW,) shall be determined for each mode according to Annex III, Appendix 1, sections 1.2.1 to 1.2.3.

When using a full flow dilution system, the total dilute exhaust gas flow rate (GTOTW,) shall be determined for each mode according to Annex III, Appendix 1, section 1.2.4."

(e)sections 1.3.2 -1.4.6 shall be replaced by the following:

1.3.2.   Dry/wet correction (GEXHW,) shall be determined for each mode according to Annex III, Appendix 1, sections 1.2.1 to 1.2.3.

When applying GEXHW the measured concentration shall be converted to a wet basis according to the following formulae, if not already measured on a wet basis:

conc (wet) = kw × conc (dry)

For the raw exhaust gas:



For the diluted gas:



or:



For the dilution air:







For the intake air (if different from the dilution air):







where:

Ha : absolute humidity of the intake air (g water per kg dry air)

Hd : absolute humidity of the dilution air (g water per kg dry air)

Rd : relative humidity of the dilution air (%)

Ra : relative humidity of the intake air (%)

pd : saturation vapour pressure of the dilution air (kPa)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa).

NOTE: H a and H d may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

1.3.3.   Humidity correction for NOx

As the NOx emission depends on ambient air conditions, the NOx concentration shall be corrected for ambient air temperature and humidity by the factors KH given in the following formula:



where:

T a : temperatures of the air in (K)

Ha : humidity of the intake air (g water per kg dry air):



where:

Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa).

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

1.3.4.   Calculation of emission mass flow rates

The emission mass flow rates for each mode shall be calculated as follows:

(a)For the raw exhaust gas (8):



(b)For the dilute exhaust gas (8):



where:

concc is the background corrected concentration



or:

DF=13,4/concCO2

The coefficients u - wet shall be used according to Table 4:

Table 4. Values of the coefficients u - wet for various exhaust components

Gasuconc
NOx0,001587ppm
CO0,000966ppm
HC0,000479ppm
CO215,19percent

The density of HC is based upon an average carbon to hydrogen ratio of 1:1,85.

1.3.5.   Calculation of the specific emissions

The specific emission (g/kWh) shall be calculated for all individual components in the following way:



where Pi = Pm,i + PAE,i.

The weighting factors and the number of modes (n) used in the above calculation are according to Annex III, section 3.7.1.

1.4.   Calculation of the particulate emission

The particulate emission shall be calculated in the following way:

1.4.1.   Humidity correction factor for particulates

As the particulate emission of diesel engines depends on ambient air conditions, the particulate mass flow rate shall be corrected for ambient air humidity with the factor Kp given in the following formula:



where:

Ha : humidity of the intake air, gram of water per kg dry air



where:

Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae

1.4.2.   Partial flow dilution system

The final reported test results of the particulate emission shall be derived through the following steps. Since various types of dilution rate control may be used, different calculation methods for equivalent diluted exhaust gas mass flow rate GEDF apply. All calculations shall be based upon the average values of the individual modes (i) during the sampling period.

1.4.2.1.   Isokinetic systems





where r corresponds to the ratio of the cross sectional areas of the isokinetic probe Ap and exhaust pipe AT:



1.4.2.2.   Systems with measurement of CO2 or NOx concentration





where:

ConcE=wet concentration of the tracer gas in raw exhaust
ConcD=wet concentration of the tracer gas in the diluted exhaust
ConcA=wet concentration of the tracer gas in the dilution air

Concentrations measured on a dry basis shall be converted to a wet basis according to section 1.3.2..

1.4.2.3.   Systems with CO2 measurement and carbon balance method



where:

CO2D=CO2 concentration of the diluted exhaust
CO2A=CO2 concentration of the dilution air

(concentrations in volume % on wet basis)

This equation is based upon the carbon balance assumption (carbon atoms supplied to the engine are emitted as CO2) and derived through the following steps:



and:



1.4.2.4.   Systems with flow measurement





1.4.3.   Full flow dilution system

The final reported test results of the particulate emission shall be derived through the following steps.

All calculations shall be based upon the average values of the individual modes (i) during the sampling period.



1.4.4.   Calculation of the particulate mass flow rate

The particulate mass flow rate shall be calculated as follows:

For the single filter method:



where:

(GEDFW)aver over the test cycle shall be determined by summation of the average values of the individual modes during the sampling period:





where i = 1,... n

For the multiple filter method:



where i = 1,...n

The particulate mass flow rate may be background corrected as follows:

For single filter method:



If more than one measurement is made, (Md/MDIL) shall be replaced with (Md/MDIL)aver



or:

DF = 13,4/concCO2

For multiple filter method:



If more than one measurement is made, (Md/MDIL) shall be replaced with (Md/MDIL)aver



or:

DF=13,4/concCO2

1.4.5.   Calculation of the specific emissions

The specific emission of particulates PT (g/kWh) shall be calculated in the following way (9):

For the single filter method:



For the multiple filter method:



1.4.6.   Effective weighting factor

For the single filter method, the effective weighting factor WFE,i for each mode shall be calculated in the following way:



where i = 1,... n.

The value of the effective weighting factors shall be within ± 0,005 (absolute value) of the weighting factors listed in Annex III, section 3.7.1."

(f)The following section shall be inserted:

"2.   DATA EVALUATION AND CALCULATIONS (NRTC TEST)

The two following measurement principles that can be used for the evaluation of pollutant emissions over the NRTC cycle are described in this section:

the gaseous components are measured in the raw exhaust gas on a real time basis, and the particulates are determined using a partial flow dilution system;

the gaseous components and the particulates are determined using a full flow dilution system (CVS system).

2.1.   Calculation of gaseous emissions in the raw exhaust gas and of the particulate emissions with a partial flow dilution system

2.1.1.   Introduction

The instantaneous concentration signals of the gaseous components are used for the calculation of the mass emissions by multiplication with the instantaneous exhaust mass flow rate. The exhaust mass flow rate may be measured directly, or calculated using the methods described in Annex III, Appendix 1, section 2.2.3 (intake air and fuel flow measurement, tracer method, intake air and air/fuel ratio measurement). Special attention shall be paid to the response times of the different instruments. These differences shall be accounted for by time aligning the signals.

For particulates, the exhaust mass flow rate signals are used for controlling the partial flow dilution system to take a sample proportional to the exhaust mass flow rate. The quality of proportionality is checked by applying a regression analysis between sample and exhaust flow as described in Annex III, Appendix 1, section 2.4.

2.1.2.   Determination of the gaseous components

2.1.2.1.   Calculation of mass emission

The mass of the pollutants M gas (g/test) shall be determined by calculating the instantaneous mass emissions from the raw concentrations of the pollutants, the u values from Table 4 (see also Section 1.3.4) and the exhaust mass flow, aligned for the transformation time and integrating the instantaneous values over the cycle. Preferably, the concentrations should be measured on a wet basis. If measured on a dry basis, the dry/wet correction as described here below shall be applied to the instantaneous concentration values before any further calculation is done.

Table 4. Values of the coefficients u - wet-for various exhaust components

Gasuconc
NOx0,001587ppm
CO0,000966ppm
HC0,000479ppm
CO215,19percent

The density of HC is based upon an average carbon to hydrogen ratio of 1:1,85.

The following formula shall be applied:



where

u=ratio between density of exhaust component and density of exhaust gas
conc i=instantaneous concentration of the respective component in the raw exhaust gas (ppm)
G EXHW,i=instantaneous exhaust mass flow (kg/s)
f=data sampling rate (Hz)
n=number of measurements

For the calculation of NOx, the humidity correction factor k H, as described here below, shall be used.

The instantaneously measured concentration shall be converted to a wet basis as described here below, if no1 already measured on a wet basis

2.1.2.2.   Dry/wet correction

If the instantaneously measured concentration is measured on a dry basis, it shall be converted to a wet basis according to the following formulae:



where



with



where

conc CO2=dry CO2 concentration (%)
conc CO=dry CO concentration (%)
H a=intake air humidity, (g water per kg dry air)



Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

2.1.2.3.   NOx correction for humidity and temperature

As the NOx emission depends on ambient air conditions, the NOx concentration shall be corrected for humidity and ambient air temperature with the factors given in the following formula:



with:

T a=temperature of the intake air, K
H a=humidity of the intake air,g water per kg dry air



where:

Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air ( kPa)

pB : total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

2.1.2.4.   Calculation of the specific emissions

The specific emissions (g/kWh) shall be calculated for each individual component in the following way:

Individual gas = M gas /W act

where

W act=actual cycle work as determined in Annex III Section 4.6.2 (kWh)

2.1.3.   Particulate determination

2.1.3.1.   Calculation of mass emission

The mass of particulates M PT (g/test) shall be calculated by either of the following methods:

(a)

where

M f=particulate mass sampled over the cycle (mg)
MSAM=mass of diluted exhaust gas passing the particulate collection filters (kg)
M EDFW=mass of equivalent diluted exhaust gas over the cycle (kg)

The total mass of equivalent diluted exhaust gas mass over the cycle shall be determined as follows:



where

G EDFW,i = instantaneous equivalent diluted exhaust mass flow rate (kg/s)

G EXHW,i = instantaneous exhaust mass flow rate (kg/s)

q i = instantaneous dilution ratio

G TOTW,I = instantaneous diluted exhaust mass flow rate through dilution tunnel (kg/s)

G DILW,i = instantaneous dilution air mass flow rate (kg/s)

f = data sampling rate (Hz)

n = number of measurements

(b)

where

M f=particulate mass sampled over the cycle (mg)
r s=average sample ratio over the test cycle

where



M SE = sampled exhaust mass over the cycle (kg)

M EXHW = total exhaust mass flow over the cycle (kg)

M SAM = mass of diluted exhaust gas passing the particulate collection filters (kg)

M TOTW = mass of diluted exhaust gas passing the dilution tunnel (kg)

NOTE: In case of the total sampling type system, M SAM and M TOTW are identical.

2.1.3.2.   Particulate correction factor for humidity

As the particulate emission of diesel engines depends on ambient air conditions, the particulate concentration shall be corrected for ambient air humidity with the factor Kp given in the following formula.



where

Ha=humidity of the intake air in g water per kg dry air



Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

2.1.3.3.   Calculation of the specific emissions

The particulate emission (g/kWh) shall be calculated in the following way:



where

W act=actual cycle work as determined in Annex III Section 4.6.2(kWh)

2.2.   Determination of gaseous and particulate components with a full flow dilution system

For calculation of the emissions in the diluted exhaust gas, it is necessary to know the diluted exhaust gas mass flow rate. The total diluted exhaust gas flow over the cycle M TOTW (kg/test) shall be calculated from the measurement values over the cycle and the corresponding calibration data of the flow measurement device (V 0 for PDP, K V for CFV, C d for SSV): the corresponding methods described in section 2.2.1 may be used. If the total sample mass of particulates (M SAM ) and gaseous pollutants exceeds 0,5% of the total CVS flow (M TOTW ), the CVS flow shall be corrected for M SAM or the particulate sample flow shall be returned to the CVS prior to the flow measuring device.

2.2.1.   Determination of the Diluted Exhaust Gas Flow

PDP-CVS system

The calculation of the mass flow over the cycle, if the temperature of the diluted exhaust is kept within ±6K over the cycle by using a heat exchanger, is as follows:



where

M TOTW=mass of the diluted exhaust gas on wet basis over the cycle
V0=volume of gas pumped per revolution under test conditions (m3/rev)
Np=total revolutions of pump per test
pB=atmospheric pressure in the test cell (kPa)
p1=pressure drop below atmospheric at the pump inlet (kPa)
T=average temperature of the diluted exhaust gas at pump inlet over thecycle (K)

If a system with flow compensation is used (i.e. without heat exchanger), the instantaneous mass emissions shall be calculated and integrated over the cycle. In this case, the instantaneous mass of the diluted exhaust gas shall be calculated as follows:



where

NP,i=total revolutions of pump per time interval

CFV-CVS system

The calculation of the mass flow over the cycle, if the temperature of the diluted exhaust gas is kept within ± 11K over the cycle by using a heat exchanger, is as follows:



where

M TOTW=mass of the diluted exhaust gas on wet basis over the cycle
t=cycle time (s)
KV=calibration coefficient of the critical flow venturi for standard conditions,
pA=absolute pressure at venturi inlet (kPa)
T=absolute temperature at venturi inlet (K)

If a system with flow compensation is used (i.e. without heat exchanger), the instantaneous mass emissions shall be calculated and integrated over the cycle. In this case, the instantaneous mass of the diluted exhaust gas shall be calculated as follows:



where

Δti=time interval(s)

SSV-CVS system

The calculation of the mass flow over the cycle is as follows if the temperature of the diluted exhaust is kept within ± 11 K over the cycle by using a heat exchanger:



where



A0 = collection of constants and units conversions

= 0,006111 in SI units of

d= diameter of the SSV throat (m)

Cd = discharge coefficient of the SSV

PA = absolute pressure at venturi inlet (kPa)

T= temperature at the venturi inlet (K)

r= ratio of the SSV throat to inlet absolute, static pressure =

ß= ratio of the SSV throat diameter, d, to the inlet pipe inner diameter =

If a system with flow compensation is used (i.e. without heat exchanger), the instantaneous mass emissions shall be calculated and integrated over the cycle. In this case, the instantaneous mass of the diluted exhaust gas shall be calculated as follows:



where



Δti=time interval (s)

The real time calculation shall be initialized with either a reasonable value for Cd, such as 0.98, or a reasonable value of Qssv. If the calculation is initialized with Qssv, the initial value of Qssv shall be used to evaluate Re.

During all emissions tests, the Reynolds number at the SSV throat must be in the range of Reynolds numbers used to derive the calibration curve developed in Appendix 2 section 3.2.

2.2.2.   NOx Correction for Humidity

As the NOx emission depends on ambient air conditions, the NOx concentration shall be corrected for ambient air humidity with the factors given in the following formulae.



where

Ta = temperature of the air (K)

Ha= humidity of the intake air (g water per kg dry air)

in which,



Ra=relative humidity of the intake air (%)
pa=saturation vapour pressure of the intake air (kPa)
pB=total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

2.2.3.   Calculation of the Emission Mass Flow

2.2.3.1.   Systems with Constant Mass Flow

For systems with heat exchanger, the mass of the pollutants MGAS (g/test) shall be determined from the following equation:



where

u=ratio between density of the exhaust component and density of diluted exhaust gas, as reported in Table 4, point 2.1.2.1
conc=average background corrected concentrations over the cycle from integration (mandatory for NOx and HC) or bag measurement (ppm)
MTOTW=total mass of diluted exhaust gas over the cycle as determined in section 2.2.1 (kg)

As the NOx emission depends on ambient air conditions, the NOx concentration shall be corrected for ambient air humidity with the factor k H, as described in section 2.2.2.

Concentrations measured on a dry basis shall be converted to a wet basis in accordance with section 1.3.2

2.2.3.1.1.   Determination of the Background Corrected Concentrations

The average background concentration of the gaseous pollutants in the dilution air shall be subtracted from measured concentrations to get the net concentrations of the pollutants. The average values of the background concentrations can be determined by the sample bag method or by continuous measurement with integration. The following formula shall be used.



where,

conc=concentration of the respective pollutant in the diluted exhaust gas, corrected by the amount of the respective pollutant contained in the dilution air (ppm)
conce=concentration of the respective pollutant measured in the diluted exhaust gas (ppm)
concd=concentration of the respective pollutant measured in the dilution air (ppm)
DF=dilution factor

The dilution factor shall be calculated as follows:



2.2.3.2.   Systems with Flow Compensation

For systems without heat exchanger, the mass of the pollutants MGAS (g/test) shall be determined by calculating the instantaneous mass emissions and integrating the instantaneous values over the cycle. Also, the background correction shall be applied directly to the instantaneous concentration value. The following formulae shall be applied:



where

conc e,i=instantaneous concentration of the respective pollutant measured in the diluted exhaust gas (ppm)
conc d=concentration of the respective pollutant measured in the dilution air (ppm)
u=ratio between density of the exhaust component and density of diluted exhaust gas, as reported in Table 4, point 2.1.2.1
M TOTW,i=instantaneous mass of the diluted exhaust gas (section 2.2.1) (kg)
M TOTW=total mass of diluted exhaust gas over the cycle (section 2.2.1) (kg)
DF=dilution factor as determined in point 2.2.3.1.1.

As the NOx emission depends on ambient air conditions, the NOx concentration shall be corrected for ambient air humidity with the factor k H, as described in section 2.2.2.

2.2.4.   Calculation of the Specific Emissions

The specific emissions (g/kWh) shall be calculated for each individual component in the following way:



where

W act=actual cycle work as determined in Annex III Section 4.6.2 (kWh)

2.2.5.   Calculation of the particulate emission

2.2.5.1.   Calculation of the Mass Flow

The particulate mass MPT (g/test) shall be calculated as follows:



Mf=particulate mass sampled over the cycle (mg)
MTOTW=total mass of diluted exhaust gas over the cycle as determined in section 2.2.1 (kg)
MSAM=mass of diluted exhaust gas taken from the dilution tunnel for collecting particulates (kg)

and,

Mf=Mf,p + Mf,b, if weighed separately (mg)
Mf,p=particulate mass collected on the primary filter (mg)
Mf,b=particulate mass collected on the back-up filter (mg)

If a double dilution system is used, the mass of the secondary dilution air shall be subtracted from the total mass of the double diluted exhaust gas sampled through the particulate filters.



where

MTOT=mass of double diluted exhaust gas through particulate filter (kg)
MSEC=mass of secondary dilution air (kg)

If the particulate background level of the dilution air is determined in accordance with Annex III, section 4.4.4, the particulate mass may be background corrected. In this case, the particulate mass (g/test) shall be calculated as follows:



where

Mf, MSAM, MTOTW = see above

MDIL = mass of primary dilution air sampled by background particulate sampler (kg)

Md = mass of the collected background particulates of the primary dilution air (mg)

DF= dilution factor as determined in section 2.2.3.1.1

2.2.5.2.   Particulate correction factor for humidity

As the particulate emission of diesel engines depends on ambient air conditions, the particulate concentration shall be corrected for ambient air humidity with the factor Kp given in the following formula.



where

Ha=humidity of the intake air in g water per kg dry air



where:

Ra : relative humidity of the intake air (%)

pa : saturation vapour pressure of the intake air (kPa)

pB : total barometric pressure (kPa)

NOTE: H a may be derived from relative humidity measurement, as described above, or from dewpoint measurement, vapour pressure measurement or dry/wet bulb measurement using the generally accepted formulae.

2.2.5.3.   Calculation of the Specific Emission

The particulate emission (g/kWh) shall be calculated in the following way:



where

Wact=actual cycle work, as determined in Annex III Section 4.6.2 (kWh)"

9)The following Appendices shall be added:

"

APPENDIX 4

NRTC ENGINE DYNAMOMETER SCHEDULE

Time

(s)
Norm. Speed

(%)
Norm. Torque

(%)
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2413
2513
2613
2713
2813
2913
3016
3116
3221
33413
34718
35921
361720
373342
385746
394433
40310
412227
423343
438049
4410547
459870
4610436
4710465
489671
4910162
5010251
5110250
5210246
5310241
5410231
55892
56820
57471
58231
5913
6018
6113
6215
6316
6414
6514
6606
6714
68921
692556
706426
716031
726320
736224
74648
755844
766510
776512
786823
796930
807130
817415
827123
837320
847321
857319
867033
877034
886547
896647
906453
916545
926638
936749
946939
956939
966642
977129
987529
997223
1007422
1017524
1027330
1037424
104776
1057612
1067439
1077230
1087522
1097864
11010234
11110328
11210328
11310319
11410332
11510425
11610338
11710339
11810334
11910244
12010338
12110243
12210334
12310241
12410344
12510337
12610327
12710413
12810430
12910419
13010328
13110440
13210432
13310163
13410254
13510252
13610251
13710340
13810434
13910236
14010444
14110344
14210433
14310227
14410326
1457953
1465137
1472423
1481333
1491955
1504530
151347
152144
153816
154156
1553947
156394
1573526
1582738
1594340
1601423
1611010
1621533
1633572
1646039
1655531
1664730
167167
16806
16908
17008
17102
172217
1731028
1742831
1753330
176360
1771910
178118
179016
18013
18114
18215
18316
18415
18513
18614
18714
18816
189818
1902051
1914919
1924113
1933116
1942821
1952117
1963121
197218
198014
199012
20038
201322
2021220
2031420
2041617
2052018
2062734
2073233
2084131
2094331
2103733
2112618
2121829
2131451
2141311
215129
2161533
2172025
2182517
2193129
2203666
2216640
2225013
2231624
2242650
2256423
2268120
2278311
2287923
2297631
2306824
2315933
232593
233257
2342110
2352019
236410
23757
23845
23946
24046
24145
24275
2431628
2442825
2455253
246508
2472640
2484829
2495439
2506042
2514818
2525451
2538890
25410384
25510385
25610284
2575866
2586497
2595680
2605167
2615296
2626362
263716
2643316
2654745
2664356
2674227
2684264
2697574
2706896
2718661
272660
273370
2744537
2756896
2768097
2779296
2789097
2798296
2809481
2819085
2829665
2837096
2845595
2857096
2867996
2878171
2887160
2899265
2908263
2916147
2925237
293240
294207
2953948
2963954
2976358
2985331
2995124
3004840
301390
3023518
3033616
3042917
3052821
3063115
3073110
3084319
3094963
3107861
3117846
3126665
3137897
3148463
3155726
3163622
3172034
318198
319910
32055
321711
3221515
323129
3241327
3251528
3261628
3271631
3281520
329170
3302034
3312125
332200
3332325
3343058
3356396
3368360
337610
338260
3392944
3406897
3418097
3428897
3439988
34410286
34510082
3467479
3475779
3487697
3498497
3508697
3518198
3528383
3536596
3549372
3556360
3567249
3575627
358290
3591813
3602511
3612824
3623453
3636583
3648044
3657746
3667650
3674552
3686198
3696169
3706349
371320
372108
373177
3741613
375116
37695
377912
3781246
3791530
3802628
381139
3821621
383244
3843643
3856585
3867866
3876339
3883234
3894655
3904742
3914239
392270
393145
3941414
3952454
3966090
3975366
3987048
3997793
4007967
4014665
4026998
4038097
4047497
4057598
4065661
407420
4083632
4093443
4106883
41110248
412620
4134139
4147186
4159152
4168955
4178956
4188858
4197869
4209839
4216461
4229034
4238838
4249762
42510053
4268158
4277451
4287657
4297672
4308572
4318460
4328372
4338372
4348672
4358972
4368672
4378772
4388872
4398871
4408772
4418571
4428872
4438872
4448472
4458373
4467773
4477473
4487672
4494677
4507862
4517935
4528238
4538141
4547937
4557835
4567838
4577846
4587549
45973
4607958
4617971
4628344
4635348
4644048
4655175
4667572
4678967
4689360
4698973
4708673
4718173
4727873
4737873
4747673
4757973
4768273
4778673
4788872
4799271
4809754
4817343
4823664
4836331
484781
4856927
4866728
487729
488719
4897836
4908156
4917553
4926045
4935037
4946641
4955161
4966847
4972942
4982473
4996471
5009071
50110061
5029473
5038473
5047973
5057572
5067873
5078073
5088173
5098173
5108373
5118573
5128473
5138573
5148673
5158573
5168573
5178572
5188573
5198373
5207973
5217873
5228173
5238272
5249456
5256648
5263571
5275144
5286023
5296410
5306314
5317037
5327645
5337818
5347651
5357533
5368117
5377645
5387630
5398014
5407118
5417114
5427111
543652
5443126
5452472
5466470
5477762
5488068
5498353
5508350
5518350
5528543
5538645
5548935
5558261
5568750
5578555
5588949
5598770
5609139
561723
5624325
5633060
5644045
5653732
5663732
5674370
5687054
5697747
5707966
5718553
5728357
5738652
5748551
5757039
576505
5773836
5783071
5797553
5808440
5818542
5828649
5838657
5848968
5859961
5867729
5878172
5888969
5894956
5907970
59110459
59210354
59310256
59410256
59510361
59610264
59710360
5989372
5998673
6007673
6015949
6024622
6034065
6047231
6057227
6066744
6076837
6086742
6096850
6107743
611584
6122237
6135769
6146838
615732
6164014
6174238
6186469
6196474
6206773
6216573
6226873
6236549
624810
6253725
6262469
6276871
6287071
6297670
6307172
6317369
6327670
6337772
6347772
6357772
6367770
6377671
6387671
6397771
6407771
6417870
6427770
6437771
6447972
6457870
6468070
6478271
6488471
6498371
6508373
6518170
6528071
6537871
6547670
6557670
6567671
6577971
6587871
6598170
6608372
6618471
6628671
6638771
6649272
6659172
6669071
6679071
6689171
6699070
6709072
6719171
6729071
6739071
6749272
6759369
6769070
6779372
6789170
6798971
6809171
6819071
6829071
6839271
6849171
6859371
6869368
6879868
6889867
68910069
6909968
69110071
6929968
69310069
69410272
69510169
69610069
69710271
69810271
69910269
70010271
70110268
70210069
70310270
70410268
70510270
70610272
70710268
70810269
70910068
71010271
71110164
71210269
71310269
71410169
71510264
71610269
71710268
71810270
71910269
72010270
72110270
72210262
72310438
72410415
72510224
72610245
72710247
72810440
72910152
73010332
73110250
73210330
73310344
73410240
73510343
73610341
73710246
73810339
73910241
74010341
74110238
74210339
74310246
74410446
74510349
74610245
74710342
74810346
74910338
75010248
75110335
75210248
75310349
75410248
75510246
75610347
75710249
75810242
75910252
76010257
76110255
76210261
76310261
76410258
76510358
76610259
76710254
76810263
76910261
77010355
77110260
77210272
77310356
77410255
77510267
77610356
7778442
778487
779486
780486
781487
782486
783487
7846721
78510559
78610596
78710574
78810566
78910562
79010566
7918941
792525
793485
794487
795485
796486
797484
798526
799515
800516
801516
802525
803525
8045744
8059890
80610594
807105100
80810598
80910595
81010596
81110592
81210497
81310085
8149474
8158762
8168150
8178146
8188039
8198032
8208128
8218026
8228023
8238023
8248020
8258119
8268018
8278117
8288020
8298124
8308121
8318026
8328024
8338023
8348022
8358121
8368124
8378124
8388122
8398122
8408121
8418131
8428127
8438026
8448026
8458125
8468021
8478120
8488321
8498315
8508312
851839
852838
853837
854836
855836
856836
857836
858836
859765
860498
861517
8625120
8637852
8648038
8658133
8668329
8678322
8688316
8698312
870839
871838
872837
873836
874836
875836
876836
877836
878594
879505
880515
881515
882515
883505
884505
885505
886505
887505
888515
889515
890515
8916350
8928134
8938125
8948129
8958123
8968024
8978124
8988128
8998127
9008122
9018119
9028117
9038117
9048117
9058115
9068015
9078028
9088122
9098124
9108119
9118121
9128120
9138326
9148063
9158059
91683100
9178173
9188353
9198076
9208161
9218050
9228137
9238249
9248337
9258325
9268317
9278313
9288310
929838
930837
931837
932836
933836
934836
935715
9364924
9376964
9388150
9398143
9408142
9418131
9428130
9438135
9448128
9458127
9468027
9478131
9488141
9498141
9508137
9518143
9528134
9538131
9548126
9558123
9568127
9578138
9588140
9598139
9608127
9618133
9628028
9638134
9648372
9658149
9668151
9678055
9688148
9698136
9708139
9718138
9728041
9738130
9748123
9758119
9768125
9778129
9788347
9798190
9808175
9818060
9828148
9838141
9848130
9858024
9868120
9878121
9888129
9898129
9908127
9918123
9928125
9938126
9948122
9958120
9968117
9978123
9988365
9998154
10008150
10018141
10028135
10038137
10048129
10058128
10068124
10078119
10088116
10098016
10108323
10118317
10128313
10138327
10148158
10158160
10168146
10178041
10188036
10198126
10208618
10218235
10227953
10238230
10248329
10258332
10268328
10277660
10287951
10298626
10308234
10318425
10328623
10338522
10348326
10358325
10368337
10378414
10388339
10397670
10407881
10417571
10428647
10438335
10448143
10458141
10467946
10478044
10488420
10497931
10508729
10518249
10528421
10538256
10548130
10558521
10568616
10577952
10587860
10597455
10607884
10618054
10628035
10638224
10648343
10657949
10668350
10678612
10686414
10692414
10704921
10717748
107210311
10739848
107410134
10759939
107610311
107710319
10781037
107910313
108010310
108110213
108210129
108310225
108410220
10859660
10869938
108710224
108810031
108910028
1090983
109110226
10929564
109310223
109410225
10959842
10969368
109710125
10989564
109910135
11009459
11019737
11029760
11039398
11049853
110510313
110610311
110710311
110810313
110910310
111010310
111110311
111210310
111310310
111410218
111510231
111610124
111710219
111810310
111910212
11209956
11219659
11227428
11236662
11247429
11256474
11266940
1127762
11287229
11296665
11305469
11316956
11326940
11337354
11346392
11356167
11367242
1137782
11387634
11396780
11407067
11415370
11427265
11436057
11447429
11456931
1146761
11477422
11487252
11496296
11505472
11517228
11527235
11536468
11547427
11557614
11566938
11576659
11586499
11595186
11607053
11617236
11627147
11637042
11646734
1165742
11667521
11677415
11687513
11697610
11707513
11717510
1172757
11737513
1174768
1175767
11766745
11777513
11787512
11797321
11806846
1181748
11827611
11837614
11847411
11857418
11867322
11877420
11887419
11897022
11907123
11917319
11927319
11937220
11946460
11957039
11966656
11976864
11983068
11997038
12006647
12017614
12027418
12036946
12046862
12056862
12066862
12076862
12086862
12096862
12105450
12114137
12122725
12131412
121400
121500
121600
121700
121800
121900
122000
122100
122200
122300
122400
122500
122600
122700
122800
122900
123000
123100
123200
123300
123400
123500
123600
123700
123800

A graphical display of the NRTC dynamometer schedule is shown below



APPENDIX 5

DURABILITY REQUIREMENTS

1. EMISSION DURABILITY PERIOD AND DETERIORATION FACTORS.

This appendix shall apply to CI engines Stage IIIA and IIIB and IV only.

1.1.Manufacturers shall determine a Deterioration Factor (DF) value for each regulated pollutant for all Stage IIIA and IIIB engine families. Such DFs shall be used for type approval and production line testing.

1.1.1.Test to establish DF's shall be conducted as follows:

1.1.1.1.The manufacturer shall conduct durability tests to accumulate engine operating hours according to a test schedule that is selected on the basis of good engineering judgement to be representative of in-use engine operation in respect to characterizing emission performance deterioration. The durability test period should typically represent the equivalent of at least one quarter of the Emission Durability Period (EDP).

Service accumulation operating hours may be acquired through running engines on a dynamometer test bed or from actual in-field machine operation. Accelerated durability tests can be applied whereby the service accumulation test schedule is performed at a higher load factor than typically experienced in the field. The acceleration factor relating the number of engine durability test hours to the equivalent number of EDP hours shall be determined by the engine manufacturer based on good engineering judgement.

During the period of the durability test, no emission sensitive components can be serviced or replaced other than to the routine service schedule recommended by the manufacturer.

The test engine, subsystems, or components to be used to determine exhaust emission DF's for an engine family, or for engine families of equivalent emission control system technology, shall be selected by the engine manufacturer on the basis of good engineering judgement. The criteria is that the test engine should represent the emission deterioration characteristic of the engine families that will apply the resulting DF values for certification approval. Engines of different bore and stroke, different configuration, different air management systems, different fuel systems can be considered as equivalent in respect to emissions deterioration characteristics if there is a reasonable technical basis for such determination.

DF values from another manufacturer can be applied if there is a reasonable basis for considering technology equivalence with respect to emissions deterioration, and evidence that the tests have been carried according to the specified requirements.

Emissions testing will be performed according to the procedures defined in this Directive for the test engine after initial run-in but before any service accumulation, and at the completion of the durability. Emission tests can also be performed at intervals during the service accumulation test period, and applied in determining the deterioration trend.

1.1.1.2.The service accumulation tests or the emissions tests performed to determine deterioration must not be witnessed by the approval authority.

1.1.1.3.Determination of DF values from Durability Tests

An additive DF is defined as the value obtained by subtraction of the emission value determine at the beginning of the EDP, from the emissions value determined to represent the emission performance at the end of the EDP.

A multiplicative DF is defined as the emission level determined for the end of the EDP divided by the emission value recorded at the beginning of the EDP.

Separate DF values shall be established for each of the pollutants covered by the legislation. In the case of establishing a DF value relative to the NOx+HC standard, for an additive DF, this is determined based on the sum of the pollutants notwithstanding that a negative deterioration for one pollutant may not offset deterioration for the other. For a multiplicative NOx+HC DF, separate HC and NOx DF's shall be determined and applied separately when calculating the deteriorated emission levels from an emissions test result before combining the resultant deteriorated NOx and HC values to esatablish compliance with the standard.

In cases where the testing is not conducted for the full EDP, the emission values at the end of the EDP is determined by extrapolation of the emission deterioration trend established for the test period, to the full EDP.

When emissions test results have been recorded periodically during the service accumulation durability testing, standard statistical processing techniques based on good practice shall be applied to determine the emission levels at the end of the EDP; statistical significance testing can be applied in the determination of the final emissions values.

If the calculation results in a value of less than 1.00 for a multiplicative DF, or less than 0.00 for an additive DF, then the DF shall be 1.0 or 0.00, respectively.

1.1.1.4.A manufacturer may, with the approval of the type approval authority, use DF values established from results of durability tests conducted to obtain DF values for certification of on-road FID CI engines. This will be allowed if there is technological equivalency between the test on-road engine and the non-road engine families applying the DF values for certification. The DF values derived from on-road engine emission durability test results, must be calculated on the basis of EDP values defined in section 2.

1.1.1.5.In the case where an engine family uses established technology, an analysis based on good engineering practices may be used in lieu of testing to determine a deterioration factor for that engine family subject to approval of the type approval authority.

1.2.DF information in approval applications

1.2.1.Additive DF's shall be specified for each pollutant in an engine family certification application for CI engines not using any aftertreatment device.

1.2.2.Multiplicative DF's shall be specified for each pollutant in an engine family certification application for CI engines using an aftertreatment device.

1.2.3.The manufacture shall furnish the Type Approval agency on request with information to support the DF values. This would typically include emission test results, service accumulation test schedule, maintenance procedures together with information to support engineering judgements of technological equivalency, if applicable.

2. EMISSION DURABILITY PERIODS FOR STAGE IIIA, IIIB AND IV ENGINES.

2.1.Manufacturers shall use the EDP in Table 1 of this section.

Table 1: EDP categories for CI Stage IIIA, IIIB and IV Engines (hours)

Category (power band)Useful life (hours)

EDP
≤ 37 kW

(constant speed engines)
3. 000
≤ 37 kW

(not constant speed engines)
5. 000
> 37 kW8. 000
Engines for the use in inland waterway vessels10. 000
Railcar engines10. 000

3.ANNEX V SHALL BE AMENDED AS FOLLOWS:

1)The heading shall be replaced by the following:

"TECHNICAL CHARACTERISTICS OF REFERENCE FUEL PRESCRIBED FOR APPROVAL TESTS AND TO VERIFY CONFORMITY OF PRODUCTION

NON-ROAD MOBILE MACHINERY REFERENCE FUEL FOR CI ENGINES TYPE APPROVED TO MEET STAGE I and II LIMIT VALUES AND FOR ENGINES TO BE USED IN INLAND WATERWAY VESSELS."

2)The following text shall be inserted after the current table on reference fuel for diesel as follows:

"NON-ROAD MOBILE MACHINERY REFERENCE FUEL FOR CI ENGINES TYPE APPROVED TO MEET STAGE IIIA LIMIT VALUES.

ParameterUnitLimits (10)Test Method
MinimumMaximum
Cetane number (11)5254,0EN-ISO 5165
Density at 15oCkg/m3833837EN-ISO 3675
Distillation:
50% pointoC245-EN-ISO 3405
95% pointoC345350EN-ISO 3405
- Final boiling point
oC-370EN-ISO 3405
Flash pointoC55-EN 22719
CFPPoC--5EN 116
Viscosity at 40oCmm2/s2,53,5EN-ISO 3104
Polycyclic aromatic hydrocarbons% m/m3,06,0IP 391
Sulphur content (12)mg/kg-300ASTM D 5453
Copper corrosion-class 1EN-ISO 2160
Conradson carbon residue (10% DR)%m/m-0,2EN-ISO 10370
Ash content%m/m-0,01EN-ISO 6245
Water content%m/m-0,05EN-ISO 12937
Neutralisation (strong acid) numbermg KOH/g-0,02ASTM D 974
Oxidation stability (13)mg/ml-0,025EN-ISO 12205

NON-ROAD MOBILE MACHINERY REFERENCE FUEL FOR CI ENGINES TYPE APPROVED TO MEET STAGE IIIB AND IV LIMIT VALUES.

ParameterUnitLimits (14)Test Method
MinimumMaximum
Cetane number (15)54,0EN-ISO 5165
Density at 15oCkg/m3833837EN-ISO 3675
Distillation:
50% pointoC245-EN-ISO 3405
95% pointoC345350EN-ISO 3405
- Final boiling point
oC-370EN-ISO 3405
Flash pointoC55-EN 22719
CFPPoC--5EN 116
Viscosity at 40oCmm2/s2,33,3EN-ISO 3104
Polycyclic aromatic hydrocarbons% m/m3,06,0IP 391
Sulphur content (16)mg/kg-10ASTM D 5453
Copper corrosion-class 1EN-ISO 2160
Conradson carbon residue (10% DR)% m/m-0,2EN-ISO 10370
Ash content% m/m-0,01EN-ISO 6245

ParameterUnitLimits (14)Test Method
Minimummaximum
Water content% m/m-0,02EN-ISO 12937
Neutralisation (strong acid) numbermg KOH/g-0,02ASTM D 974
Oxidation stability (17)mg/ml-0,025EN-ISO 12205
Lubricity (HFRR wear scar diameter at 60oC)µm-400CEC F-06-A-96
FAMEprohibited

4.ANNEX VII SHALL BE AMENDED AS FOLLOWS:

APPENDIX 1 SHALL BE REPLACED BY THE FOLLOWING:

"Appendix 1

TEST RESULTS FOR COMPRESSION IGNITION ENGINES TEST RESULTS







5.ANNEX XII SHALL BE AMENDED AS FOLLOWS:

The following section shall be added:

"3.For engines categories H, I, and J (stage IIIA) and engines category K, L and M (stage IIIB) as defined in Article 9 section 3, the following type-approvals and, where applicable, the pertaining approval marks are recognised as being equivalent to an approval to this Directive;

3.1.Type-approvals to Directive 88/77/EEC, as amended by Directive 99/96/EC, which are in compliance with stages B1, B2 or C provided for in Article 2 and section 6.2.1 of Annex I.

3.2.UN-ECE Regulation 49.03 series of amendments which are in compliance with stages B1, B2 and C provided for in paragraph 5.2."



(1) Note 1 shall be amended as follows: Identical with C1 cycle as described in Paragraph 8.3.1.1 of the ISO8178-4: 2002(E) standard.

(2) Note 2 shall be amended as follows: Identical with D2 cycle as described in Paragraph 8.4.1 of the ISO8178-4: 2002(E) standard.

(3) Constant-speed auxiliary engines must be certified to the ISO D2 duty cycle, i.e. the 5-mode steady-state cycle specified in Section 3.7.1.2., while variable-speed auxiliary engines must be certified to the ISO C1 duty cycle, i.e. the 8-mode steady-state cycle specified in Section 3.7.1.1.

(4) Identical with E3 cycle as described in Sections 8.5.1, 8.5.2 and 8.5.3 of the ISO8178-4: 2002(E) standard. The four modes lie on an average propeller curve based on in-use measurements.

(5) Identical with E2 cycle as described in Sections8.5.1, 8.5.2 and 8.5.3 of the ISO8178-4: 2002(E) standard.

(6) Identical with F cycle of ISO 8178-4: 2002 (E) standard."

(7) The calibration procedure is common for both NRSC and NRTC tests, with the exception of the requirements specified in Sections 1.11 and 2.6.

(8) In the case of NOx, the NOx concentration (NOxconc or NOxconcc) has to be multiplied by KHNOx (humidity correction factor for NOx quoted in section 1.3.3) as follows: KHNOx x conc or KHNOx x concc

(9) The participate mass flow rate PTmass has to be multiplied by Kp (humidity correction factor for particulates quoted in section 1.4.1).

(10) The values quoted in the specifications are "true values". In establishment of their limit values the terms of ISO 4259 "Petroleum products - Determination and application of precision data in relation to methods of test" have been applied and in fixing a minimum value, a minimum difference of 2R above zero has been taken into account; in fixing a maximum and minimum value, the minimum difference is 4R (R = reproducibility).

Notwithstanding this measure, which is necessary for technical reasons, the manufacturer of fuels should nevertheless aim at a zero value where the stipulated maximum value is 2R and at the mean value in the case of quotations of maximum and minimum limits. Should it be necessary to clarify the questions as to whether a fuel meets the requirements of the specifications, the terms of ISO 4259 should be applied.

(11) The range for cetane number is not in accordance with the requirements of a minimum range of 4R. However, in the case of a dispute between fuel supplier and fuel user, the terms of ISO 4259 may be used to resolve such disputes provided replicate measurements, of sufficient number to archive the necessary precision, are made in preference to single determinatio

(12) The actual sulphur content of the fuel used for the test shall be reported..

(13) Even though oxidation stability is controlled, it is likely that shelf life will be limited. Advice should be sought from the supplier as to storage conditions and life.

(14) The values quoted in the specifications are "true values". In establishment of their limit values the terms of ISO 4259 "Petroleum products - Determination and application of precision data in relation to methods of test" have been applied and in fixing a minimum value, a minimum difference of 2R above zero has been taken into account; in fixing a maximum and minimum value, the minimum difference is 4R (R = reproducibility).

Notwithstanding this measure, which is necessary for technical reasons, the manufacturer of fuels should nevertheless aim at a zero value where the stipulated maximum value is 2R and at the mean value in the case of quotations of maximum and minimum limits. Should it be necessary to clarify the questions as to whether a fuel meets the requirements of the specifications, the terms of ISO 4259 should be applied.

(15) The range for cetane number is not in accordance with the requirements of a minimum range of 4R. However, in the case of a dispute between fuel supplier and fuel user, the terms of ISO 4259 may be used to resolve such disputes provided replicate measurements, of sufficient number to archive the necessary precision, are made in preference to single determinations.

(16) The actual sulphur content of the fuel used for the Type I test shall be reported.

(17) Even though oxidation stability is controlled, it is likely that shelf life will be limited. Advice should be sought from the supplier as to storage conditions and life."



ANNEX II

"Annex VI

ANALYTICAL AND SAMPLING SYSTEM

1. GASEOUS AND PARTICULATE SAMPLING SYSTEMS

Figure NumberDescription
2Exhaust gas analysis system for raw exhaust
3Exhaust gas analysis system for dilute exhaust
4Partial flow, isokinetic flow, suction blower control, fractional sampling
5Partial flow, isokinetic flow, pressure blower control, fractional sampling
6Partial flow, CO2 or NOx control, fractional sampling
7Partial flow, CO2 or carbon balance, total sampling
8Partial flow, single venturi and concentration measurement, fractional sampling
9Partial flow, twin venturi or orifice and concentration measurement, fractional sampling
10Partial flow, multiple tube splitting and concentration measurement, fractional sampling
11Partial flow, flow control, total sampling
12Partial flow, flow control, fractional sampling
13Full flow, positive displacement pump or critical flow venturi, fractional sampling
14Particulate sampling system
15Dilution system for full flow system

1.1.   Determination of the gaseous emissions

Section 1.1.1 and Figures 2 and 3 contain detailed descriptions of the recommended sampling and analysing systems. Since various configurations can produce equivalent results, exact conformance with these figures is not required. Additional components such as instruments, valves, solenoids, pumps and switches may be used to provide additional information and coordinate the functions of the component systems. Other components which are not needed to maintain the accuracy on some systems, may be excluded if their exclusion is based upon good engineering judgement.

1.1.1.   Gaseous exhaust components CO, CO2, HC, NOx

An analytical system for the determination of the gaseous emissions in the raw or diluted exhaust gas is described based on the use of:

HFID analyser for the measurement of hydrocarbons,

NDIR analysers for the measurement of carbon monoxide and carbon dioxide,

HCLD or equivalent analyser for the measurement of nitrogen oxide.

For the raw exhaust gas (Figure 2), the sample for all components may be taken with one sampling probe or with two sampling probes located in close proximity and internally split to the different analysers. Care must be taken that no condensation of exhaust components (including water and sulphuric acid) occurs at any point of the analytical system.

For the diluted exhaust gas (Figure 3), the sample for the hydrocarbons shall be taken with another sampling probe than the sample for the other components. Care must be taken that no condensation of exhaust components (including water and sulphuric acid) occurs at any point of the analytical system.

Figure 2

Flow diagram of exhaust gas analysis system for CO, NOx and HC



Figure 3

Flow diagram of dilute exhaust gas analysis system for CO, CO2, NOx and HC



Descriptions – Figures 2 and 3

General statement:

All components in the sampling gas path must be maintained at the temperature specified for the respective systems.

SP1 raw exhaust gas sampling probe (Figure 2 only)

A stainless steel straight closed and multihole probe is recommended. The inside diameter shall not be greater than the inside diameter of the sampling line. The wall thickness of the probe shall not be greater than 1 mm. There shall be a minimum of three holes in three different radial planes sized to sample approximately the same flow. The probe must extend across at least 80% of the diameter of the exhaust pipe.

SP2 dilute exhaust gas HC sampling probe (Figure 3 only)

The probe shall:

be defined as the first 254 mm to 762 mm of the hydrocarbon sampling line (HSL3),

have a 5 mm minimum inside diameter,

be installed in the dilution tunnel DT (section 1.2.1.2) at a point where the dilution air and exhaust gas are well mixed (i.e. approximately 10 tunnel diameters downstream of the point where the exhaust enters the dilution tunnel),

be sufficiently distant (radially) from other probes and the tunnel wall so as to be free from the influence of any wakes or eddies,

be heated so as to increase the gas stream temperature to 463 K (190oC) ± 10 K at the exit of the probe.

SP3 dilute exhaust gas CO, CO2, NOx sampling probe (Figure 3 only)

The probe shall:

be in the same plane as SP2,

be sufficiently distant (radially) from other probes and the tunnel wall so as to be free from the influence of any wakes or eddies,

be heated and insulated over its entire length to a minimum temperature of 328 K (55oC) to prevent water condensation.

HSL1 heated sampling line

The sampling line provides gas sampling from a single probe to the split point(s) and the HC analyser.

The sampling line shall:

have a 5 mm minimum and a 13,5 mm maximum inside diameter,

be made of stainless steel or PTFE,

maintain a wall temperature of 463 (190oC) ± 10 K as measured at every separately controlled heated section, if the temperature of the exhaust gas at the sampling probe is equal or below 463 K (190oC),

maintain a wall temperature greater than 453 K (180oC) if the temperature of the exhaust gas at the sampling probe is above 463 K (190oC),

maintain a gas temperature of 463 K (190oC) ± 10 K immediately before the heated filter (F2) and the HFID.

HSL2 heated NOx sampling line

The sampling line shall:

maintain a wall temperature of 328 to 473 K (55 to 200oC) up to the converter when using a cooling bath, and up to the analyser when a cooling bath is not used,

be made of stainless steel or PTFE.

Since the sampling line need only be heated to prevent condensation of water and sulphuric acid, the samplingline temperature will depend on the sulphur content of the fuel.

SL sampling line for CO (CO2)

The line shall be made of PTFE or stainless steel. It may be heated or unheated.

BK background bag (optional; Figure 3 only)

For the measurement of the background concentrations.

BG sample bag (optional; Figure 3 CO and CO2 only)

For the measurement of the sample concentrations.

F1 heated pre-filter (optional)

The temperature shall be the same as HSL1.

F2 heated filter

The filter shall extract any solid particles from the gas sample prior to the analyser. The temperature shall be the same as HSL1. The filter shall be changed as needed.

P heated sampling pump

The pump shall be heated to the temperature of HSL1.

HC

Heated flame ionization detector (HFID) for the determination of the hydrocarbons. The temperature shall be kept at 453 to 473 K (180 to 200oC).

CO, CO2

NDIR analysers for the determination of carbon monoxide and carbon dioxide.

NO2

(H)CLD analyser for the determination of the oxides of nitrogen. If a HCLD is used it shall be kept at a temperature of 328 to 473 K (55 to 200oC).

C converter

A converter shall be used for the catalytic reduction of NO2 to NO prior to analysis in the CLD or HCLD.

B cooling bath

To cool and condense water from the exhaust sample. The bath shall be maintained at a temperature of 273 to 277 K (0 to 4oC) by ice or refrigeration. It is optional if the analyser is free from water vapour interference as determined in Annex III, Appendix 2, sections 1.9.1 and 1.9.2.

Chemical dryers are not allowed for removing water from the sample.

T1, T2, T3 temperature sensor

To monitor the temperature of the gas stream.

T4 temperature sensor Temperature of the NO2-NO converter.

T5 temperature sensor

To monitor the temperature of the cooling bath.

G1, G2, G3 pressure gauge

To measure the pressure in the sampling lines.

R1, R2 pressure regulator

To control the pressure of the air and the fuel, respectively, for the HFID.

R3, R4, R5 pressure regulator

To control the pressure in the sampling lines and the flow to the analysers.

FL1, FL2, FL3 flow meter

To monitor the sample bypass flow.

FL4 to FL7 flow meter (optional)

To monitor the flow rate through the analysers.

V1 to V6 selector valve

Suitable valving for selecting sample, span gas or zero gas flow to the analyser.

V7, V8 solenoid valve

To bypass the NO2-NO converter.

V9 needle valve

To balance the flow through the NO2-NO converter and the bypass.

V10, V11 needle valve

To regulate the flows to the analysers.

V12, V13 toggle valve

To drain the condensate from the bath B.

V14 selector valve

Selecting the sample or background bag.

1.2.   Determination of the particulates

Sections 1.2.1 and 1.2.2 and Figures 4 to 15 contain detailed descriptions of the recommended dilution and sampling systems. Since various configurations can produce equivalent results, exact conformance with these figures is not required. Additional components such as instruments, valve, solenoids, pumps and switches may be used to provide additional information and coordinate the functions of the component systems. Other components which are not needed to maintain the accuracy on some systems, may be excluded if their exclusion is based on good engineering judgement.

1.2.1.   Dilution system

1.2.1.1.   Partial flow dilution system (Figures 4 to 12) (1)

A dilution system is described based on the dilution of a part of the exhaust stream. Splitting of the exhaust stream and the following dilution process may be done by different dilution system types. For subsequent collection of the particulates, the entire dilute exhaust gas or only a portion of the dilute exhaust gas may be passed to the particulate sampling system (section 1.2.2, Figure 14). The first method is referred to as total sampling type, the second method as fractional sampling type.

The calculation of the dilution ratio depends on the type of system used.

The following types are recommended:

isokinetic systems (Figures 4 and 5)

With these systems, the flow into the transfer tube is matched to the bulk exhaust flow in terms of gas velocity and/or pressure, thus requiring an undisturbed and uniform exhaust flow at the sampling probe. This is usually achieved by using a resonator and a straight approach tube upstream of the sampling point. The split ratio is then calculated from easily measurable values like tube diameters. It should be noted that isokinesis is only used for matching the flow conditions and not for matching the size distribution. The latter is typically not necessary, as the particles are sufficiently small as to follow the fluid streamlines,

flow controlled systems with concentration measurement (Figures 6 to 10)

With these systems, a sample is taken from the bulk exhaust stream by adjusting the dilution air flow and the total dilution exhaust flow. The dilution ratio is determined from the concentrations of tracer gases, such as CO2 or NOx, naturally occurring in the engine exhaust. The concentrations in the dilution exhaust gas and in the dilution air are measured, whereas the concentration in the raw exhaust gas can be either measured directly or determined from fuel flow and the carbon balance equation, if the fuel composition is known. The systems may be controlled by the calculated dilution ratio (Figures 6 and 7) or by the flow into the transfer tube (Figures 8, 9 and 10),

flow controlled systems with flow measurement (Figures 11 and 12)

With these systems, a sample is taken from the bulk exhaust stream by setting the dilution air flow and the total dilution exhaust flow. The dilution ratio is determined from the difference of the two flow rates. Accurate calibration of the flow meters relative to one another is required, since the relative magnitude of the two flow rates can lead to significant errors at higher dilution ratios. Flow control is very straightforward by keeping the dilute exhaust flow rate constant and varying the dilution air flow rate, if needed.

In order to realise the advantages of the partial flow dilution systems, attention must be paid to avoiding the potential problems of loss of particulates in the transfer tube, ensuring that a representative sample is taken from the engine exhaust, and determination of the split ratio.

The systems described pay attention to these critical areas.

Figure 4

Partial flow dilution system with isokinetic probe and fractional sampling (SB control)



Raw exhaust gas is transferred from the exhaust pipe to EP to the dilution tunnel DT through the transfer tube TT by the isokinetic sampling probe ISP. The differential pressure of the exhaust gas between exhaust pipe and inlet to the probe is measured with the pressure transducer DPT. This signal is transmitted to the flow controller FC1 that controls the suction blower SB to maintain a differential pressure of zero at the tip of the probe. Under these conditions, exhaust gas velocities in EP and ISP are identical, and the flow through ISP and TT is a constant fraction (split) of the exhaust gas flow. The split ratio is determined from the cross sectional areas of EP and ISP. The dilution air flow rate is measured with the flow measurement device FM1. The dilution ratio is calculated from the dilution air flow rate and the split ratio.

Figure 5

Partial flow dilution system with isokinetic probe and fractional sampling (PB control)



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the transfer tube TT by the isokinetic sampling probe ISP. The differential pressure of the exhaust gas between exhaust pipe and inlet to the probe is measured with the pressure transducer DPT. This signal is transmitted to the flow controller FC1 that controls the pressure blower PB to maintain a differential pressure of zero at the tip of the probe. This is done by taking a small fraction of the dilution air whose flow rate has already been measured with the flow measurement device FM1, and feeding it to TT by means of a pneumatic orifice. Under these conditions, exhaust gas velocities in EP and ISP are identical, and the flow through ISP and TT is a constant fraction (split) of the exhaust gas flow. The split ratio is determined from the cross sectional areas of EP and ISP. The dilution air is sucked through DT by the suction blower SB, and the flow rate is measured with FM1 at the inlet to DT. The dilution ratio is calculated from the dilution air flow rate and the split ratio.

Figure 6

Partial flow dilution system with CO2 or NOx concentration measurement and fractional sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT. The concentrations of a tracer gas (CO2 or NOx) are measured in the raw and diluted exhaust gas as well as in the dilution air with the exhaust gas analyser(s) EGA. These signals are transmitted to the flow controller FC2 that controls either the pressure blower PB or the suction blower SB to maintain the desired exhaust split and dilution ratio in DT. The dilution ratio is calculated from the tracer gas concentrations in the raw exhaust gas, the diluted exhaust gas, and the dilution air.

Figure 7

Partial flow dilution system with CO2 concentration measurement, carbon balance and total sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT. The CO2 concentrations are measured in the diluted exhaust gas and in the dilution air with the exhaust gas analyser(s) EGA. The CO2 and fuel flow GFUEL signals are transmitted either to the flow controller FC2, or to the flow controller FC3 of the particulate sampling system (Figure 14). FC2 controls the pressure blower PB, while FC3 controls the particulate sampling system (Figure 14), thereby adjusting the flows into and out of the system so as to maintain the desired exhaust split and dilution ratio in DT. The dilution ratio is calculated from the CO2 concentrations and GFUEL using the carbon balance assumption.

Figure 8

Partial flow dilution system with single venturi, concentration measurement and fractional sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT due to the negative pressure created by the venturi VN in DT. The gas flow rate through TT depends on the momentum exchange at the venturi zone, and is therefore affected by the absolute temperature of the gas at the exit of TT. Consequently, the exhaust split for a given tunnel flow rate is not constant, and the dilution ratio at low load is slightly lower than at high load. The tracer gas concentrations (CO2 or NOx) are measured in the raw exhaust gas, the diluted exhaust gas, and the dilution air with the exhaust gas analyser(s) EGA, and the dilution ratio is calculated from the values so measured.

Figure 9

Partial flow dilution system twin venturi or twin orifice, concentration measurement and fractional sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT by a flow divider that contains a set of orifices or venturis. The first one (FD1) is located in EP, the second one (FD2) in TT. Additionally, two pressure control valves (PCV1 and PCV2) are necessary to maintain a constant exhaust split by controlling the backpressure in EP and the pressure in DT. PC VI is located downstream of SP in EP, PCV2 between the pressure blower PB and DT. The tracer gas concentrations (CO2 or NOx) are measured in the raw exhaust gas, the diluted exhaust gas, and the dilution air with the exhaust gas analyser(s) EGA. They are necessary for checking the exhaust split, and may be used to adjust PCV1 and PCV2 for precise split control. The dilution ratio is calculated from the tracer gas concentrations.

Figure 10

Partial flow dilution system with multiple tube splitting, concentration measurement and fractional sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the transfer tube TT by the flow divider FD3 that consists of a number of tubes of the same dimensions (same diameter, length and bed radius) installed in EP. The exhaust gas through one of these tubes is lead to DT, and the exhaust gas through the rest of the tubes is passed through the damping chamber DC. Thus, the exhaust split is determined by the total number of tubes. A constant split control requires a differential pressure of zero between DC and the outlet of TT, which is measured with the differential pressure transducer DPT. A differential pressure of zero is achieved by injecting fresh air into DT at the outlet of TT. The tracer gas concentrations (CO2 or NOx) are measured in the raw exhaust gas, the diluted exhaust gas, and the dilution air with the exhaust gas analyser(s) EGA. They are necessary for checking the exhaust split and may be used to control the injection air flow rate for precise split control. The dilution ratio is calculated from the tracer gas concentrations.

Figure 11

Partial flow dilution system with flow control and total sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT. The total flow through the tunnel is adjusted with the flow controller FC3 and the sampling pump P of the particulate sampling system (Figure 16).

The dilution air flow is controlled by the flow controller FC2, which may use GEXH, GAIR or GFUEL as command signals, for the desired exhaust split. The sample flow into DT is the difference of the total flow and the dilution air flow. The dilution air flow rate is measured with flow measurement device FM1, the total flow rate with the flow measurement device FM3 of the particulate sampling system (Figure 14). The dilution ratio is calculated from these two flow rates.

Figure 12

Partial flow dilution system with flow control and fractional sampling



Raw exhaust gas is transferred from the exhaust pipe EP to the dilution tunnel DT through the sampling probe SP and the transfer tube TT. The exhaust split and the flow into DT is controlled by the flow controller FC2 that adjusts the flows (or speeds) of the pressure blower PB and the suction blower SB, accordingly. This is possible since the sample taken with the particulate sampling system is returned into DT. GEXH, GAIR or GFUEL may be used as command signals for FC2. The dilution air flow rate is measured with the flow measurement device FM1, the total flow with the flow measurement device FM2. The dilution ratio is calculated from these two flow rates.

Description - Figures 4 to 12

EP exhaust pipe

The exhaust pipe may be insulated. To reduce the thermal inertia of the exhaust pipe a thickness to diameter ratio of 0,015 or less is recommended. The use of flexible sections shall be limited to a length to diameter ratio of 12 or less. Bends will be minimised to reduce inertial deposition. If the system includes a test bed silencer, the silencer may also be insulated.

For an isokinetic system, the exhaust pipe must be free of elbows, bends and sudden diameter changes for at least six pipe diameters upstream and three pipe diameters downstream of the tip of the probe. The gas velocity at the sampling zone must be higher than 10 m/s except at idle mode. Pressure oscillations of the exhaust gas must not exceed ± 500 Pa on the average. Any steps to reduce pressure oscillations beyond using a chassis-type exhaust system (including silencer and after-treatment device) must not alter engine performance nor cause the deposition of particulates.

For systems without isokinetic probes, it is recommended to have a straight pipe of six pipe diameters upstream and three pipe diameters downstream of the tip of the probe.

SP sampling probe (Figures 6 to 12)

The minimum inside diameter shall be 4 mm. The minimum diameter ratio between exhaust pipe and probe shall be four. The probe shall be an open tube facing upstream on the exhaust pipe centre-line, or a multiple hole probe as described under SP1 in section 1.1.1.

ISP isokinetic sampling probe (Figures 4 and 5)

The isokinetic sampling probe must be installed facing upstream on the exhaust pipe centre-line where the flow conditions in section EP are met, and designed to provide a proportional sample of the raw exhaust gas. The minimum inside diameter shall be 12 mm.

A control system is necessary for isokinetic exhaust splitting by maintaining a differential pressure of zero between EP and ISP. Under these conditions exhaust gas velocities in EP and ISP are identical and the mass flow through ISP is a constant fraction of the exhaust gas flow. The ISP has to be connected to a differential pressure transducer. The control to provide a differential pressure of zero between EP and ISP is done with blower speed or flow controller.

FD1, FD2 flow divider (Figure 9)

A set of venturis or orifices is installed in the exhaust pipe EP and in the transfer tube TT, respectively, to provide a proportional sample of the raw exhaust gas. A control system consisting of two pressure control valves PCV1 and PCV2 is necessary for proportional splitting by controlling the pressures in EP and DT.

FD3 flow divider (Figure 10)

A set of tubes (multiple tube unit) is installed in the exhaust pipe EP to provide a proportional sample of the raw exhaust gas. One of the tubes feeds exhaust gas to the dilution tunnel DT, whereas the other tubes exit exhaust gas to a damping chamber DC. The tubes must have the same dimensions (same diameter, length, bend radius), so that the exhaust split depends on the total number of tubes. A control system is necessary for proportional splitting by maintaining a differential pressure of zero between the exit of the multiple tube unit into DC and the exit of TT. Under these conditions, exhaust gas velocities in EP and FD3 are proportional, and the flow TT is a constant fraction of the exhaust gas flow. The two points have to be connected to a differential pressure transducer DPT. The control to provide a differential pressure of zero is done with the flow controller FC1.

EGA exhaust gas analyser (Figures 6 to 10)

CO2 or NOx analysers may be used (with carbon balance method CO2 only). The analysers shall be calibrated like the analysers for the measurement of the gaseous emissions. One or several analysers may be used to determine the concentration differences.

The accuracy of the measuring systems has to be such that the accuracy of GEDFW,i is within ± 4%.

TT transfer tube (Figures 4 to 12)

The particulate sample transfer tube shall be:

as short as possible, but not more than 5 m in length,

equal to or greater than the probe diameter, but not more than 25 mm in diameter,

exiting on the centre-line of the dilution tunnel and pointing down-stream.

If the tube is 1 metre or less in length, it is to be insulated with material with a maximum thermal conductivity of 0,05 W/(m · K) with a radial insulation thickness corresponding to the diameter of the probe. If the tube is longer than 1 metre, it must be insulated and heated to a minimum wall temperature of 523 K (250oC).

Alternatively, the transfer tube wall temperatures required may be determined through standard heat transfer calculations.

DPT differential pressure transducer (Figures 4, 5 and 10)

The differential pressure transducer shall have a range of ± 500 Pa or less.

FC1 flow controller (Figures 4, 5 and 10)

For the isokinetic systems (Figures 4 and 5) a flow controller is necessary to maintain a differential pressure of zero between EP and ISP. The adjustment can be done by:

(a)controlling the speed or flow of the suction blower (SB) and keeping the speed of the pressure blower (PB) constant during each mode (Figure 4);

or

(b)adjusting the suction blower (SB) to a constant mass flow of the diluted exhaust and controlling the flow of the pressure blower PB, and therefore the exhaust sample flow in a region at the end of the transfer tube (TT) (Figure 5).

In the case of a pressure controlled system the remaining error in the control loop must not exceed ± 3 Pa. The pressure oscillations in the dilution tunnel must not exceed ± 250 Pa on average.

For a multi-tube system (Figure 10) a flow controller is necessary for proportional exhaust splitting to maintain a differential pressure of zero between the outlet of the multi-tube unit and the exit of TT. The adjustment can be done by controlling the injection air flow rate into DT at the exit of TT.

PCV1, PCV2 pressure control valve (Figure 9)

Two pressure control valves are necessary for the twin venturi/twin orifice system for proportional flow splitting by controlling the backpressure of EP and the pressure in DT. The valves shall be located downstream of SP in EP and between PB and DT.

DC damping chamber (Figure 10)

A damping chamber shall be installed at the exit of the multiple tube unit to minimize the pressure oscillations in the exhaust pipe EP.

VN venturi (Figure 8)

A venturi is installed in the dilution tunnel DT to create a negative pressure in the region of the exit of the transfer tube TT. The gas flow rate through TT is determined by the momentum exchange at the venturi zone, and is basically proportional to the flow rate of the pressure blower PB leading to a constant dilution ratio. Since the momentum exchange is affected by the temperature at the exit of TT and the pressure difference between EP and DT, the actual dilution ratio is slightly lower at low load than at high load.

FC2 flow controller (Figures 6, 7, 11 and 12; optional)

A flow controller may be used to control the flow of the pressure blower PB and/or the suction blower SB. It may be connected to the exhaust flow or fuel flow signal and/or to the CO2 or NOx differential signal.

When using a pressurized air supply (Figure 11) FC2 directly controls the air flow.

FM1 flow measurement device (Figures 6, 7, 11 and 12)

Gas meter or other flow instrumentation to measure the dilution air flow. FM1 is optional if PB is calibrated to measure the flow.

FM2 flow measurement device (Figure 12)

Gas meter or other flow instrumentation to measure the diluted exhaust gas flow. FM2 is optional if the suction blower SB is calibrated to measure the flow.

PB pressure blower (Figures 4, 5, 6, 7, 8, 9 and 12)

To control the dilution air flow rate, PB may be connected to the flow controllers FC1 or FC2. PB is not required when using a butterfly valve. PB may be used to measure the dilution air flow, if calibrated.

SB suction blower (Figures 4, 5, 6, 9, 10 and 12)

For fractional sampling systems only. SB may be used to measure the dilute exhaust gas flow, if calibrated.

DAF dilution air filter (Figures 4 to 12)

It is recommended that the dilution air be filtered and charcoal scrubbed to eliminate background hydrocarbons. The dilution air shall have a temperature of 298 K (25oC) ± 5 K.

At the manufacturer's request the dilution air shall be sampled according to good engineering practice to determine the background particulate levels, which can then be subtracted from the values measured in the diluted exhaust.

PSP particulate sampling probe (Figures 4, 5, 6, 8, 9, 10 and 12)

The probe is the leading section of PTT and

shall be installed facing upstream at a point where the dilution air and exhaust gas are well mixed, i.e. on the dilution tunnel DT centre-line of the dilution systems approximately 10 tunnel diameters downstream of the point where the exhaust enters the dilution tunnel,

shall be 12 mm in minimum inside diameter,

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel,

may be insulated.

DT dilution tunnel (Figures 4 to 12)

The dilution tunnel:

shall be of a sufficient length to cause complete mixing of the exhaust and dilution air under turbulent flow conditions,

shall be constructed of stainless steel with:

a thickness to diameter ratio of 0,025 or less for dilution tunnels of greater than 75 mm inside diameter,

a nominal wall thickness of not less than 1,5 mm for dilution tunnels of equal to or less than 75 mm inside diameter,

shall be at least 75 mm in diameter for the fractional sampling type,

is recommended to be at least 25 mm in diameter for the total sampling type.

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel.

may be insulated.

The engine exhaust shall be thoroughly mixed with the dilution air. For fractional sampling systems, the mixing quality shall be checked after introduction into service by means of a CO2 profile of the tunnel with the engine running (at least four equally spaced measuring points). If necessary, a mixing orifice may be used.

NOTE: If the ambient temperature in the vicinity of the dilution tunnel (DT) is below 293 K (20oC), precautions should be taken to avoid particle losses onto the cool walls of the dilution tunnel. Therefore, heating and/or insulating the tunnel within the limits given above is recommended.

At high engine loads, the tunnel may be cooled by a non-aggressive means such as a circulating fan, as long as the temperature of the cooling medium is not below 293 K (20oC).

HE heat exchanger (Figures 9 and 10)

The heat exchanger shall be of sufficient capacity to maintain the temperature at the inlet to the suction blower SB within ± 11 K of the average operating temperature observed during the test.

1.2.1.2.   Full flow dilution system (Figure 13)

A dilution system is described based upon the dilution of the total exhaust using the constant volume sampling (CVS) concept. The total volume of the mixture of exhaust and dilution air must be measured. Either a PDP or a CFV or a SSV system may be used.

For subsequent collection of the particulates, a sample of the dilute exhaust gas is passed to the particulate sampling system (section 1.2.2, Figures 14 and 15). If this is done directly, it is referred to as single dilution. If the sample is diluted once more in the secondary dilution tunnel, it is referred to as double dilution. This is useful, if the filter face temperature requirement cannot be met with single dilution. Although partly a dilution system, the double dilution system is described as a modification of a particulate sampling system in section 1.2.2, (Figure 15), since it shares most of the parts with a typical particulate sampling system.

The gaseous emissions may also be determined in the dilution tunnel of a full flow dilution system. Therefore, the sampling probes for the gaseous components are shown in Figure 13 but do not appear in the description list. The respective requirements are described in section 1.1.1.

Descriptions (Figure 13)

EP exhaust pipe

The exhaust pipe length from the exit of the engine exhaust manifold, turbocharger outlet or after-treatment device to the dilution tunnel is required to be not more than 10 m. If the system exceeds 4 m in length, then all tubing in excess of 4 m shall be insulated, except for an in-line smoke-meter, if used. The radial thickness of the insulation must be at least 25 mm. The thermal conductivity of the insulating material must have a value no greater than 0,1 W/(m · K) measured at 673 K (400oC). To reduce the thermal inertia of the exhaust pipe a thickness to diameter ratio of 0,015 or less is recommended. The use of flexible sections shall be limited to a length to diameter ratio of 12 or less.

Figure 13

Full flow dilution system



The total amount of raw exhaust gas is mixed in the dilution tunnel DT with the dilution air. The diluted exhaust gas flow rate is measured either with a positive displacement pump PDP or with a critical flow venturi CFV or with a sub-sonic venturi SSV. A heat exchanger FIE or electronic flow compensation EFC may be used for proportional particulate sampling and for flow determination. Since particulate mass determination is based on the total diluted exhaust gas flow, the dilution ratio is not required to be calculated.

PDP positive displacement pump

The PDP meters total diluted exhaust flow from the number of the pump revolutions and the pump displacement. The exhaust system back pressure must not be artificially lowered by the PDP or dilution air inlet system. Static exhaust back pressure measured with the CVS system operating shall remain within ± 1,5 kPa of the static pressure measured without connection to the CVS at identical engine speed and load.

The gas mixture temperature immediately ahead of the PDP shall be within ± 6 K of the average operating temperature observed during the test, when no flow compensation is used.

Flow compensation can only be used if the temperature at the inlet of the PDP does not exceed 50oC (323 K).

CFV critical flow venturi

CFV measures total diluted exhaust flow by maintaining the flow at choked conditions (critical flow). Static exhaust backpressure measured with the CFV system operating shall remain within ± 1,5 kPa of the static pressure measured without connection to the CFV at identical engine speed and load. The gas mixture temperature immediately ahead of the CFV shall be within ± 11 K of the average operating temperature observed during the test, when no flow compensation is used.

SSV sub-sonic venturi

SSV measures total diluted exhaust flow as a function of inlet pressure, inlet temperature, pressure drop between the SSV inlet and throat. Static exhaust backpressure measured with the SSV system operating shall remain within ± 1,5 kPa of the static pressure measured without connection to the SSV at identical engine speed and load. The gas mixture temperature immediately ahead of the SSV shall be within ± 11 K of the average operating temperature observed during the test, when no flow compensation is used.

HE heat exchanger (optional if EFC is used)

The heat exchanger shall be of sufficient capacity to maintain the temperature within the limits required above.

EFC electronic flow compensation (optional if HE is used)

If the temperature at the inlet to either the PDP or CFV or SSV is not kept within the limits stated above, a flow compensation system is required for continuous measurement of the flow rate and control of the proportional sampling in the particulate system. To that purpose, the continuously measured flow rate signals are used to correct the sample flow rate through the particulate filters of the particulate sampling system (Figures 14 and 15), accordingly.

DT dilution tunnel

The dilution tunnel:

shall be small enough in diameter to cause turbulent flow (Reynolds number greater than 4000) of sufficient length to cause complete mixing of the exhaust and dilution air. A mixing orifice may be used,

shall be at least 75 mm in diameter,

may be insulated.

The engine exhaust shall be directed downstream at the point where it is introduced into the dilution tunnel, and thoroughly mixed.

When using single dilution, a sample from the dilution tunnel is transferred to the particulate sampling system (section 1.2.2, Figure 14). The flow capacity of the PDP or CFV or SSV must be sufficient to maintain the diluted exhaust at a temperature of less than or equal to 325 K (52oC) immediately before the primary particulate filter.

When using double dilution, a sample from the dilution tunnel is transferred to the secondary dilution tunnel where it is further diluted, and then passed through the sampling filters (section 1.2.2, Figure 15). The flow capacity of the PDP or CFV or SSV must be sufficient to maintain the diluted exhaust stream in the DT at a temperature of less than or equal to 464 K (191oC) at the sampling zone. The secondary dilution system must provide sufficient secondary dilution air to maintain the doubly-diluted exhaust stream at a temperature of less than or equal to 325 K (52oC) immediately before the primary particulate filter.

DAF dilution air filter

It is recommended that the dilution air be filtered and charcoal scrubbed to eliminate background hydrocarbons. The dilution air shall have a temperature of 298 K (25oC) ± 5 K. At the manufacturer's request the dilution air shall be sampled according to good engineering practice to determine the background particulate levels, which can then be subtracted from the values measured in the diluted exhaust.

PSP particulate sampling probe

The probe is the leading section of PTT and

shall be installed facing upstream at a point where the dilution air and exhaust gas are well mixed, i.e. on the dilution tunnel DT centre-line of the dilution systems approximately 10 tunnel diameters downstream of the point where the exhaust enters the dilution tunnel,

shall be 12 mm in minimum inside diameter,

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel,

may be insulated.

1.2.2.   Particulate sampling system (Figures 14 and 15)

The particulate sampling system is required for collecting the particulates on the particulate filter. In the case of total sampling partial flow dilution, which consists of passing the entire dilute exhaust sample through the filters, dilution (section 1.2.1.1, Figures 7 and 11) and sampling system usually form an integral unit. In the case of fractional sampling partial flow dilution or full flow dilution, which consists of passing through the filters only a portion of the diluted exhaust, the dilution (section 1.2.1.1, Figures 4, 5, 6, 8, 9, 10 and 12 and section 1.2.1.2, Figure 13) and sampling systems usually form different units.

In this Directive, the double dilution system DDS (Figure 15) of a full flow dilution system is considered as a specific modification of a typical particulate sampling system as shown in Figure 14. The double dilution system includes all important parts of the particulate sampling system, like filter holders and sampling pump, and additionally some dilution features, like a dilution air supply and a secondary dilution tunnel.

In order to avoid any impact on the control loops, it is recommended that the sample pump be running throughout the complete test procedure. For the single filter method, a bypass system shall be used for passing the sample through the sampling filters at the desired times. Interference of the switching procedure on the control loops must be minimized.

Descriptions - Figures 14 and 15

PSP particulate sampling probe (Figures 14 and 15)

The particulate sampling probe shown in the figures is the leading section of the particulate transfer tube PTT. The probe:

shall be installed facing upstream at a point where the dilution air and exhaust gas are well mixed, i.e. on the dilution tunnel DT centre-line of the dilution systems (section 1.2.1), approximately 10 tunnel diameters downstream of the point where the exhaust enters the dilution tunnel),

shall be 12 mm in minimum inside diameter,

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air pre-heating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel,

may be insulated.

Figure 14

Particulate sampling system



A sample of the diluted exhaust gas is taken from the dilution tunnel DT of a partial flow or full flow dilution system through the particulate sampling probe PSP and the particulate transfer tube PTT by means of the sampling pump P. The sample is passed through the filter holders(s) FH that contain the particulate sampling filters. The sample flow rate is controlled by the flow controller FC3. If electronic flow compensation EFC (Figure 13) is used, the diluted exhaust gas flow is used as command signal for FC3.

Figure 15

Dilution system (full flow system only)



A sample of the diluted exhaust gas is transferred from the dilution tunnel DT of a full flow dilution system through the particulate sampling probe PSP and the particulate transfer tube PTT to the secondary dilution tunnel SDT, where it is diluted once more. The sample is then passed through the filter holder(s) FH that contain the particulate sampling filters. The dilution air flow rate is usually constant whereas the sample flow rate is controlled by the flow controller FC3. If electronic flow compensation EFC (Figure 13) is used, the total diluted exhaust gas flow is used as command signal for FC3.

PTT particulate transfer tube (Figures 14 and 15)

The particulate transfer tube must not exceed 1 020 mm in length, and must be minimised in length whenever possible.

The dimensions are valid for:

the partial flow dilution fractional sampling type and the full flow single dilution system from the probe tip to the filter holder,

the partial flow dilution total sampling type from the end of the dilution tunnel to the filter holder,

the full flow double dilution system from the probe tip to the secondary dilution tunnel.

The transfer tube:

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel,

may be insulated.

SDT secondary dilution tunnel (Figure 15)

The secondary dilution tunnel should have a minimum diameter of 75 mm and should be sufficient length so as to provide a residence time of at least 0,25 seconds for the doubly-diluted sample. The primary filter holder, FH, shall be located within 300 mm of the exit of the SDT. The secondary dilution tunnel:

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC) prior to the introduction of the exhaust in the dilution tunnel,

may be insulated.

FH filter holder(s) (Figures 14 and 15)

For primary and back-up filters one filter housing or separate filter housings may be used. The requirements of Annex III, Appendix 1, section 1.5.1.3 have to be met.

The filter holder(s):

may be heated to no greater than 325 K (52oC) wall temperature by direct heating or by dilution air preheating, provided the air temperature does not exceed 325 K (52oC),

may be insulated.

P sampling pump (Figures 14 and 15)

The particulate sampling pump shall be located sufficiently distant from the tunnel so that the inlet gas temperature is maintained constant (± 3 K), if flow correction by FC3 is not used.

DP dilution air pump (Figure 15) (full flow double dilution only)

The dilution air pump shall be located so that the secondary dilution air is supplied at a temperature of 298 K (25oC) ± 5 K.

FC3 flow controller (Figures 14 and 15)

A flow controller shall be used to compensate the particulate sample flow rate for temperature and backpressure variations in the sample path, if no other means are available. The flow controller is required if electronic flow compensation EFC (Figure 13) is used.

FM3 flow measurement device (Figures 14 and 15) (particulate sample flow)

The gas meter or flow instrumentation shall be located sufficiently distant from the sample pump so that the inlet gas temperature remains constant (± 3 K), if flow correction by FC3 is not used.

FM4 flow measurement device (Figure 15) (dilution air, full flow double dilution only)

The gas meter or flow instrumentation shall be located so that the inlet gas temperature remains at 298 K (25 oC) ± 5K.

BV ball valve (optional)

The ball valve shall have a diameter not less than the inside diameter of the sampling tube and a switching time of less than 0,5 seconds.

NOTE: If the ambient temperature in the vicinity of PSP, PTT, SDT, and FH is below 239 K (20oC), precautions should be taken to avoid particle losses onto the cool wall of these parts. Therefore, heating and/or insulating these parts within the limits given in the respective descriptions is recommended. It is also recommended that the filter face temperature during sampling be not below 293 K (20oC).

At high engine loads, the above parts may be cooled by a non-aggressive means such as a circulating fan, as long as the temperature of the cooling medium is not below 293 K (20oC).



(1) Figures 4 to 12 show many types of partial flow dilution systems, which normally can be used for the steady-state test (NRSC). But, because of very severe constraints of the transient tests, only those partial flow dilution systems (Figures 4 to 12) able to fulfill all the requirements quoted in the section "Partial flow dilution system specifications" of Annex III, Appendix 1, Section 2.4, are accepted for the transient test (NRTC).



ANNEX III

"Annex XIII

PROVISIONS FOR ENGINES PLACED ON THE MARKET UNDER A "FLEXIBLE SCHEME"

On the request of an equipment manufacturer (OEM), and permission being granted by an approval authority, an engine manufacturer may during the period between two successive stages of limit values place a limited number of engines on the market that only comply with the previous stage of emission limit values in accordance with the following provisions:

1. ACTIONS BY THE ENGINE MANUFACTURER AND THE OEM

1.1.An OEM that wishes to make use of the flexibility scheme shall request permission from any approval authority to purchase from his engine suppliers, in the period between two emissions stages, the quantities of engines described in sections 1.2 and 1.3, that do not comply with the current emission limit values, but are approved to the nearest previous stage of emission limits.

1.2.The number of engines placed on the market under a flexibility scheme shall, in each engine category, not exceed 20% of the OEM's annual sales of equipment with engines in that engine category (calculated as the average of the latest 5 years sales on the EU market). Where an OEM has marketed equipment in the EU for a period of less than 5 years the average will be calculated based on the period for which the OEM has marketed equipment in the EU.

1.3.As an optional alternative option to section 1.2, the OEM may seek permission for his engine suppliers to place on the market a fixed number of engines under the flexibility scheme. The number of engines in each engine category shall not exceed the following values:

Engine CategoryNumber of Engines
19-37kW200
37-75kW150
75-130kW100
130-560kW50

1.4.The OEM shall include in his application to an approval authority the following information:

(a)a sample of the labels to be affixed to each piece of non-road mobile machinery in which an engine placed on the market under the flexibility scheme will be installed. The labels shall bear the following text: "MACHINE NO ... (sequence of machines) OF ... (total number of machines in respective power band) WITH ENGINE No ... WITH TYPE APPROVAL (Dir. 97/68/EC) No ..."; and

(b)a sample of the supplementary label to be affixed on the engine bearing the text referred to in section 2.2 of this Annex.

1.5.The OEM shall notify the approval authorities of each Member State of the use of the flexibility scheme.

1.6.The OEM shall provide the approval authority with any information connected with the implementation of the flexibility scheme that the approval authority may request as necessary for the decision.

1.7.The OEM shall file a report every six months to the approval authorities of each Member State on the implementation of the flexibility schemes he is using. The report shall include cumulative data on the number of engines and NRMM placed on the market under the flexibility scheme, engine and NRMM serial numbers, and the Member States where the NRMM have been placed on the market. This procedure shall be continued as long as a flexibility scheme is still in progress.

2. ACTIONS BY THE ENGINE MANUFACTURER

2.1.An engine manufacturer may place on the market engines under a flexible scheme covered by an approval in accordance with Section 1 of this Annex.

2.2.The engine manufacturer must put a label on those engines with the following text: "Engine placed on the market under the flexibility scheme".

3. ACTIONS BY THE APPROVAL AUTHORITY

3.1.The approval authority shall evaluate the content of the flexibility scheme request and the enclosed documents. As a consequence it will inform the OEM of its decision as to whether or not to allow use of the flexibility scheme.



ANNEX IV

The following Annexes shall be added:

"

Annex XIV

CCNR stage I (1)

PN

(kW)
CO

(g/kWh)
HC

(g/kWh)
NOx

(g/k/Wh)
PT

(g/kWh)
37 ≤ PN < 756,51,39,20,85
75 ≤ PN < 1305,01,39,20,70
P ≥ 1305,01,3n ≥ 2800 tr/min = 9.2

500 ≤ n < 2800 tr/min = 45 x n (-0.2)
0,54

Annex XV

CCNR stage II (2)

PN

(kW)
CO

(g/kWh)
HC

(g/kWh)
NOx

(g/kWh)
PT

(g/kWh)
18 ≤ PN < 375,51,58,00,8
37 ≤ PN < 755,01,37,00,4
75 ≤ PN < 1305,01,06,00,3
130 ≤ PN < 5603,51,06,00,2
PN ≥ 5603,51,0n ≥ 3150 min-1 = 6,0

343 ≤ n < 3150 min-1 = 45 x n(-0,2) - 3

n < 343 mm-1 =11,0
0,2

"


(1) CCNR Protocol 19, Resolution of the Central Commission for the Navigation of the Rhine of 11 May 2000

(2) CCNR Protocol 21, Resolution of the Central Commission for the Navigation of the Rhine of 31 May 2001.